F06 Inlet Temperature Sensor (C1) in Heat Exchanger Trouble
Error Detection Method
Error Diagnosis
1.
2.
In case of open or short
•
Outdoor unit control PCB failure
Replace PCB with a new one.
Is the connector properly connected to PCB?
1-1
Is the resistor between the sockets infinity or 0Ω?
1-2
2-1
1-2
Reconnect & check.
Replace sensor.
2-1
Yes
No
1 Sensor
Trouble
2 Control
PCB
Failure
Yes
No
F07 Intermediate Temperature Sensor (C2) in Heat Exchanger Trouble
Error Detection Method
Error Diagnosis
It is judged an error when open circuit or short circuit.
1.
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check.
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor.
2-1
Yes
No
F08 Outdoor Air Temperature Sensor (TO) Trouble
Error Detection Method
1.
It is judged an error when open circuit or short circuit.
Error Diagnosis
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check.
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor.
2-1
Yes
No
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 12
18/01/26 14:0 :17
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...