1-11-3
1
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from
all outdoor units
except any one of the outdoor units. (When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
<Type E3>
CAUTION
(3) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
: Branch point
More than 2m required
(4) Use shielded wires for inter-unit control wiring (C) and ground the shield on both sides, otherwise misoperation from
noise may occur.
Connect wiring as shown in Section “ Wiring System Diagrams” on page 1-11-2.
(Functional earthing)
(Functional earthing)
Shielded wire
(5) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR)
rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245 IEC66)
SM830276-00_欧州向け R32シングル TD&SM.indb 3
2019/02/27 11:54:22
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...