1-12-2-2-5
1
Installing the Drain Pipe
CAUTION
●
Do not apply force to the drain port when connecting the
drain pipe. Install and fix it near the indoor unit as close
as possible.
●
Do not use adhesive when connecting the drain port pipe
and the drain hose.
(1) How to Install the Drain Pipe
1) First insert the supplied hose band into the drain port
pipe. Then make sure the head of the screw is facing
toward a technical engineer when placing the screw of
the hose band at an upward angle.
2) Insert the soft PVC socket of the supplied drain hose
to the drain port pipe. Do not use adhesive when
connecting the drain hose to the drain port pipe.
Insert it until the tip of the drain hose contacts the uneven
surface of the drain port pipe.
3) Move the hose band so that the center position of the
hose band can be placed approx. 30 mm away from the
external plate of the indoor unit. See diagram below.
4) Screw the drain hose tightly facing the screw of the hose
band upward. (Torque: 2.5 N·m - 3.4 N·m) (If the screw
is tightened beneath the drain hose, the troubles will be
generated.)
5) Apply approx. 2
g
of adhesive on both sides of the drain
hose without connection of the hard PVC socket and the
hard PVC pipe joint (VP25) in the local supply.
6) Connect the drain hose and the hard PVC pipe joint so
that the adhesive area of both sides can be overlapped.
Wipe off the protrusion-adhesive with a soft cloth.
Drain port
Do not use adhesive here.
* Drain port may possibly
be damaged and cause
the water leakage if
PVC adhesive is used.
* After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
Fasten the hose band as shown the diagram
below. (Torque: 2.5 N·m - 3.4 N·m)
Note:
Be sure to tightly insert the hard PVC pipe joint
(including elbow) minimum 20 mm or more.
57 mm
20 mm or more
Drain insulator
(supplied)
* However, do not use the hard PVC
pipe joint allowable more than 55 mm
insertion.
Packing
(supplied)
Adhere with PVC adhesive.
* Apply approx. 2
g
of adhesive on both sides
of supplied the drain hose and the hard
PVC pipe joint (VP25) in the local supply.
Wipe off the protrusion-adhesive with a soft
cloth.
Hard PVC pipe joint
(VP25 field supplied)
Hard PVC socket
Hose band (supplied)
Soft PVC socket
Drain hose
(supplied)
Uneven
surface
Indoor
unit
Indoor
unit
Uneven surface
5 mm
(Drainage check section
on drain port, transparent)
281258_EU.indb 11
2016-9-1 13:03:44
12
Checking the Drainage
Be careful since the fan will start
when you short the pin on the
indoor control board.
After wiring (
S
ee the
“1-11
. E
LECTRICAL WIRING”
.) and drain
piping are completed, use the following procedure to check
that the water will drain smoothly. For this, prepare a bucket
and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L, N
terminals) inside the electrical component box.
(2) Slowly pour about 1 L of water into the drain pan to
check drainage.
Drainage check
Over 100 mm
Plastic container for
water intake
Water (Approx. 1 L)
Drain pan outlet
(3) Short the check pin (CHK) (6P : 5-6) on the indoor
control board and operate the drain pump. Check the
water flow through the transparent drain pipe and see if
there is any leakage.
* If the check pin (CHK) (6P:5-6) is shorted, the fan starts
rotating at high speed and could cause injury.
(4) When the check of drainage is complete, open the check
pin (CHK) (6P : 5-6) and remount the tube cover.
(5) Checkpoint after installation
After installation of indoor and outdoor units, panels
and electrical wiring, check the
following items.
CAUTION
Important Note for Wiring 4-Way Cassette Type
(1) The power supply inlet is located at the lower area of
the refrigerant tubing side of the unit. The electrical
component box is located at the air intake of the bottom
of the unit.
(2) Before installing the panel for cassette, be sure to carry
out the wiring connection.
(3) Remove the lid located on the bottom of the indoor unit
attaching the electrical component box by unscrewing
the Phillips head tapping screws (×2).
(4) Lead the wires from the power supply inlet to the unit.
Be sure to lead the wires through the power supply inlet.
Make sure that no wire is caught between the indoor unit
and panel for cassette. Otherwise, the unit may cause a
fire.
(5) Connect the wires into the terminals through the power
supply inlet for the electrical component box.
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its
original position with paying attention not to have the
wires caught in the lid.
See the
“
1-11
. E
LECTRICAL
W
IRING
”.
Power supply inlet
Tapping screw position
281258_EU.indb 12
2016-9-1 13:03:44
SM830276-00_欧州向け R32シングル TD&SM.indb 5
2019/02/27 11:54:53
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...