1-12-2-1-10
1
1-4. Indoor Fan Performance
9
8
7
6
5
4
3
2
1
M
L
M
M
M
M
M
H
H
H
H
H
H
L
L
L
L
L
Item code “
”
Setting at
shipment
Cooling
Heating
Cooling
Heating
Cooling
Heating
Tap
Type 200
Type 250
(External static pressure 75 Pa)
(External static pressure 120 Pa)
(External static pressure 180 Pa)
(External static pressure 75 Pa)
(External static pressure 130 Pa)
(External static pressure 200 Pa)
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
Limit line
H
H
M
M
L
L
2
4
7
9
6
8
H
H
H
M
M
M
L
L
L
1
2
4
7
9
6
8
3
5
H
M
L
1
3
5
External static pressure (Pa)
External static pressure (Pa)
External static pressure (Pa)
External static pressure (Pa)
External static pressure (Pa)
External static pressure (Pa)
Air Volume (m
3
/min)
Air Volume (m
3
/min)
Air Volume (m
3
/min)
Air Volume (m
3
/min)
Air Volume (m
3
/min)
Air Volume (m
3
/min)
0
10
20
30
40
50
60
70
80
90
100
110
120
45 50 55 60 65 70 75 80 85
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0
10
20
30
40
50
60
70
80
90
100
110
120
20
40
60
80
100
120
140
160
180
200
60
80
100
120
140
160
180
200
220
240
260
130
50 55 60 65 70 75 80 85 90 95 100
50 55 60 65 70 75 80 85 90 95 100
50 55 60 65 70 75 80 85 90 95 100
45 50 55 60 65 70 75 80 85
60
80
100
120
140
160
180
200
220
45 50 55 60 65 70 75 80 85
Fig. 1-12-2-1-4
START
[ ]
20:30 (THU)
How to set the external static pressure
1. Keep pressing the , and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
2. Press the or button to see beach menu. If
you wish to see the next screen instantly, press the
or button.
Select “8. Detailed settings” on the LCD display and press the
button.
The “Detailed settings” screen appears on the LCD display.
Select the “Unit no.” by pressing the or button
for changes.
,
Maintenance func
0. ECONAVI info.
1. Outdoor unit error data
2. Service contact
3. RC setting mode
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
Detailed settings
Unit no.
Code no.
Set data
10
3-1
0006
Sel.
Next
20:30 (THU)
3. Select the “Code no.” by pressing the or
button.
Change the “Code no.” to “5D” by pressing the or
button (or keeping it pressed).
4. Select the “Set data” by pressing the or
button.
Select one of the “Set data” among “0006”, “0003” or “0001”
according to the desired external static pressure setting by
pressing the or button.
(See Table 1-12-2-1-4 and Fig. 1-12-2-1-4.)
Then press the button.
5. Select the “Unit no.” by pressing the or
button and press the button.
The “Exit detailed settings and restart?”
(Detailed setting-end) screen appears on the LCD display.
Select “YES” and press the button.
Detailed settings
Unit no.
Code no.
Set data
1
0
0
0
1
-
3
Sel.
Next
20:30 (THU)
5D
Table 1-12-2-1-4 Setting the external static pressure
Indoor unit
Item code
200
250
5D
External static pressure of the rated
air
fl
ow volume
180 Pa
200 Pa
0006
120 Pa
130 Pa
0003
75 Pa
75 Pa
0001
Detailed settings
Unit no.
Code no.
Set data
10
1-1
0001
Sel.
Next
20:30 (THU)
Exit detailed settings
and restart?
NO
YES
1-3. Operating the High-spec Wired Remote Controller (CZ-RTC5B)
SM830276-00_欧州向け R32シングル TD&SM.indb 10
2019/02/27 11:54:46
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...