5-12
5
F06 Inlet Temperature Sensor (C1) in Heat Exchanger Trouble
Error Detection Method
Error Diagnosis
1.
2.
In case of open or short
•
Outdoor unit control PCB failure
Replace PCB with a new one.
Is the connector properly connected to PCB?
1-1
Is the resistor between the sockets infinity or 0 ohm?
1-2
2-1
1-2
Reconnect & check
Replace sensor.
2-1
Yes
No
1 Sensor
Trouble
2 Control
PCB
Failure
Yes
No
F07 Intermediate Temperature Sensor (C2) in Heat Exchanger Trouble
Error Detection Method
Error Diagnosis
It is judged an error when open circuit or short circuit.
1.
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor
2-1
Yes
No
F08 Outdoor Air Temperature Sensor (TO) Trouble
Error Detection Method
1.
It is judged an error when open circuit or short circuit.
Error Diagnosis
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor
2-1
Yes
No
SM830276-00_欧州向け R32シングル TD&SM.indb 12
19/02/28 13:29:24
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...