1-12-2-1-7
1
1-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is
placed. (Fig. 1-12-2-1-3)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to
the Table 1-12-2-1-2.
Table 1-12-2-1-2 External static pressure SW setting
External static pressure at the
time of rated airflow volume
SW001
200
250
TP6
TP3
TP1
180Pa
200Pa
ON
1
2
3
120Pa
130Pa
1
ON
2
3
75Pa
75Pa
1
2
ON
3
Table 1-12-2-1-3 Setting the external static pressure
Indoor unit
Item code
200
250
External static pressure of the rated
air flow volume
180 Pa
200 Pa
120 Pa
130 Pa
75 Pa
75 Pa
A
°
°
1
5
6
2
1
4
1
3
1
4
NOTE:
Failure to set this parameter may result in
decreased air
fl
ow and condensation.
1. Press and hold down the , and buttons
simultaneously for 4 or more seconds. ( , the
Unit No., Item Code and Detailed Data will blink on
the LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select button
is pressed .
Only the fan motor for the selected indoor unit will operate
during this time.
3. Specify the “ ” item code by pressing the
buttons for the temperature setting buttons and confirm
the values. (“ ” set at shipment)
4. Press the buttons for the time to amend the
values for the set data. Refer to Table 1-12-2-1-3 and
Fig. 1-12-2-1-4 and select a value “ ”, “ ” or
“ ”.
5. Press the button.
The display will stop blinking and remain illuminated.
6. Press the button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
/
/
/
/
1
ON
TP
6
TP
3
TP
1
2
SW001
3
1
TP
6
TP
3
TP
1
2
SW001
3
ON
Indoor Unit control PC board
Setting at
shipment
Fig. 1-12-2-1-3
1-2. Operating the Timer Remote Controller (CZ-RTC4)
How to set the external static pressure
EXTERNAL STATIC PRESSURE SETTING
Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below) and make settings.
a. No setting changes:
When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b. Manual setting (on PCB):
This is static pressure setting excepting factory preset at shipment. Dip switch select method.
c. Manual setting (by timer remote controller):
Static pressure setting excepting factory preset at shipment.
Flow of External Static Pressure
NOTE
(1) Refer to Tables 1-12-2-1-3, 1-12-2-1-4 and Fig. 1-12-2-1-4 for details on the relationship between the value of item code
“5d” and the external static pressure.
(2) When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor unit to item code “5d”.
When amending the setting after selecting [b. Manual setting] (due to airflow path changes, etc.), it is necessary to cancel
[b. Manual setting] (switching OFF positions).
When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual setting] takes
precedence when the power is switched back on after power outages, etc.
CAUTION
Make sure the external static pressure is in a range of specifications.
Then proceed the external static pressure setting.
Improper settings can cause noise, a shortage of airflow volume and water leakage.
Refer to Fig. 1-12-2-1-4 for the external static pressure setting range.
Be sure to set the [External Static Pressure Setting] once again after amending the airflow path
for the duct or air outlet after setting the external static pressure.
Start of external static pressure setting
Setting of shipment :
line 5
Is it designed and
installed at the setting line at
shipment on PQ line drawing?
See section 1-4.
Operating by timer
remote controller
Selection methods
of external static
pressure setting
No
No
Yes
Yes
a. No setting changes
b. Manual setting
(Setting on PCB)
Setting switches of TP6 or TP3 or TP1
See section “1-1. How to set on PC
Board”.
c. Manual setting
Item code 5d : Setting 1, 3, 6
(*Note 1) (*Note 2)
See section 1-2. or 1-3.
Completion of external static pressure setting
SM830276-00_欧州向け R32シングル TD&SM.indb 7
2019/02/27 11:54:45
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...