5-28
5
Mini VRF SYSTEM
Trouble Diagnosis
4. Mini VRF System Alarm Codes
1-1
2-1
Correct the connector
connections
Yes
No
3-1
Replace the outdoor
fan motor
Yes
No
1 Wiring
2
Disconnect the connectors “CN-FM_UP” and “CN-FM_LO” from
the outdoor control PC board and rotate the outdoor fan by
hand; does it rotate freely?
(Check the outdoor fan motor lock)
2-1
Outdoor
fan motor
P22 Outdoor Unit Fan Motor Trouble
Error Detection Method
Error Diagnosis
It is judged an error when the outdoor fan motor’s rotating signal cannot be detected normally.
•
1.
2.
Are the connectors “CN-FM_UP” and “CN-FM_LO” firmly
connected to the outdoor control PC board (lock engaged)?
3
Turn the power on and run the unit again; is P22 triggered
again? Or can you see or hear anything that is obviously
wrong in its rotation?
Replace the outdoor control PC board. (If it fails to operate normally even after replacing
the outdoor control PC board, replace the outdoor fan motor.)
3-1
3-2
3-3 If there is nothing particularly out of the ordinary, see what happens.
Outdoor
control
PC board
3-2
3-3
Yes
No
SM830276-00_欧州向け R32シングル TD&SM.indb 28
19/02/28 13:29:38
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...