1-12-2-2-11
1
(2) Removing the corner cover
Push the latches on the corner cover in the direction of
the arrow
1
and remove them by sliding in the direction
of the arrow
2
.
2
1
1
(3) Installing the panel for cassette
The power must be turned ON in order to change the
flap angle. (Do not attempt to move the flap by hand.
Doing so may damage the flap.)
1) Hang the temporary latches on the inside of the panel
for cassette to the receptacle on the unit to temporarily
attach the panel for cassette in place.
●
The panel for cassette must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the panel for cassette corner with
the correct positions on the unit.
●
When removing the panel for cassette, push the
temporary latches outward while holding the panel for
cassette.
Receptacle on the
main unit
Push to disengage.
Temporary latch
Temporary latches (×2)
2) Align the panel installation holes and the unit screw holes.
3) Tighten the provided washer head screws at the
4 panel installation locations so that the panel is
attached tightly to the unit.
Corner cover
Corner cover
Push latches upward
to disengage.
Panel for cassette
Strap
4) Check that the panel is attached tightly to the ceiling.
●
At this time, make sure that there are no gaps
between the unit and the panel for cassette, or
between the panel for cassette and the ceiling surface.
●
If there is a gap between the panel and the ceiling,
leave the panel for cassette attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.
CAUTION
●
If the screws are not sufficiently tightened, trouble
such as that shown in the figure below may occur.
Be sure to tighten the screws securely.
●
If a gap remains between the ceiling surface and the
panel for cassette even after the screws are tightened,
adjust the height of the unit again.
Make fine adjustment by a wrench or
other tools to the installation height
of the unit to eliminate the gap with
the ceiling through the holes of the
corner cover.
Do not allow gaps.
Panel for cassette
Main unit
Ceiling surface
Drain tube corner
Refrigerant tube
corner
Marking with DRAIN
Marking with REF. PIPE
Washer head screws
(preinstalled on the
panel for cassette)
Panel for cassette
Air leakage
Staining
Air leakage
from panel for cassette
Condensation, water leakage
Adjust so that there
are no gaps.
If there is no affect to the horizontal of the unit and
drain tube, adjustment to the installation height of the
unit can be made through the hole of the panel for
cassette corner.
281258_EU.indb 20
2016-9-1 13:03:59
(4) Wiring the Panel for Cassette
1) Open the cover of the electrical component box for
control PCB.
2) Connect the 22P connector (white) from the panel for
cassette to the connector on the control PCB in the
unit electrical component box. In this case, expose the
cutout section of the tube for the wiring protection to
the outside from the electrical component box and fix it
with the clamper attached to the electrical component
box.
Insert connector lock facing PCB edge until it is
locked in place. (If not connected completely, the
Auto Flap will not operate and “P09” is displayed
on the remote controller. When the connector
plugged in the wrong direction, parts on the PCB
may be damaged.)
Check that the wiring connector is not caught
between the electrical component box and the
cover.
Check that the wiring connector is not caught
between the unit and the panel for cassette.
(5) How to Attach the Corner & Air-Intake Grille
A. Attaching the corner cover
1) Check that the safety cord from the corner cover is
fastened to the panel for cassette pin, as shown in the
figure below.
2) Use the supplied screws to attach the corner cover to the
panel for cassette.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for
“Removing the grille” in the reverse order. By rotating the
air-intake grille, it is possible to attach the grille onto the
panel for cassette from any of 4 directions. Coordinate the
directions of the air-intake grilles when installing multiple
units, and change the directions according to customer’s
requests.
When attaching the air-intake grille, be careful that the
flap lead wire does not become caught.
Be sure to attach the safety cord that prevents the air-
intake grille from dropping off to the panel for cassette
unit as shown in the figure below.
With this panel for cassette, the directions of the air-
intake grille lattices when installing multiple units, and the
position of the label showing the company name on the
corner panel, can be changed according to customer’s
requests, as shown in the figure below. However, the
wireless signal receiver can only be installed at the
refrigerant-tubing corner of the ceiling unit.
Hole of panel for cassette hook
Refrigerant tube side
Optional wireless receiver kit
* This position is only possible for
installation.
Corner cover installation position
marked with the Panasonic Logo at
shipment.
* Installation possible at any of 4
corners
Electrical
component box
Can be installed
rotated 90°
Locations of air-intake grille hinges at
shipment
* The grille can be installed with these
hinges facing in any of 4 directions.
Drain pipe side
Hook that prevents the grille from dropping
Pin
Place the corner cover
so that the 5 tabs fit into
the holes in the panel
for cassette. Then
fasten it in place with
the supplied screws.
Supplied screw
Lid of electrical component box
Screws (×2)
22P (white)
Cutout section of the tube
for wiring protection
Panel for cassette
wiring connector
Wiring diagram
(Direction that the unit
faces has been changed to
facilitate explanation.)
Connector
Lock
SM830276-00_欧州向け R32シングル TD&SM.indb 11
2019/02/27 11:55:05
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...