96
Settings for energy saving
Energy saving
6
Set other outdoor units.
z
Repeat steps 3 to 5.
7
Touch [Register].
z
To cancel the settings, touch [Cancel].
7
Item
Explanation
Start time
End time
Set the start and end times for “Timer 1” and
“Timer 2”.
Use
to set the time.
The setting ranges are as follows.
y
Hours: 00 to 23 (1 hour intervals)
y
Minutes: 00 to 59 (1 minute intervals)
Note
y
You can make the settings extend over
different dates.
For example: 22:00 to 08:00
Demand
Select an operation.
No operation is caused if you select [----].
When you have selected [Ope.] in “Demand”,
set the control rate with
. The
values shown are those values that can be
set for the outdoor unit selected.
Demand/peak
shaving Valid
The outdoor unit time slot demand control
setting is enabled for the selected outdoor
unit if you put a check mark here.
5
Touch [Register].
z
The “Setting” dialogue closes.
z
To cancel the settings, touch [Cancel].
5
Suppressing the consumption of electricity/gas [Demand/peak shaving settings]/[Peak cut settings]
Note
y
The settings for peak cut (when using gas heat pump air conditioners) are made in the same way as outdoor time slot demand settings.