165
Configuring the system
Setting
Note
y
You can register a maximum of 50 event controls.
y
You can register a maximum of 32 conditions each for input points and output points for each individual event.
13
Set the output delay time.
(1) Touch [OutptDlayTme].
z
The “OutptDlayTme” settings dialogue is displayed.
13-
1
(2) Select the output delay time.
z
Set the initiating time for the output point when the input
point conditions have been met.
13-
2
14
Put a check mark next to “Valid”.
z
The set event control works if you put a check mark here.
14
15
Touch [Register].
z
To cancel the settings, touch [Cancel].
15
Linked control of air conditioning units