Temperature Input (cont.)
4.
One of the following two prompts will appear, depending on your selection in Step 3.
• If
Fixed
was chosen, enter the known fixed process temperature and press
[Enter]
.
The meter will only accept
values from –328° to 1832°F (–200
o
to 1000
o
C).
• If
Slot 1
was chosen, scroll to the desired temperature input (from A to D) and press
[Enter].
5.
At the
Temp Return
prompt, scroll to
Fixed
to enter a constant temperature value or on
Slot1
to select the output
in
Slot 1
that will provide the live temperature input for the return.
Note:
If Slot 1 contains an activated option card with an analog input assigned to
TEMP
or an
RTD
input, Slot 1
appears as an option at the above prompt. If the process temperature is stable, a fixed value may be used,
but most applications require a live temperature input.
6.
One of the following two prompts will appear, depending on your selection in Step 3.
• If
Fixed
was chosen, enter the known fixed process temperature and press
[Enter].
The meter will only accept
values from –328° to 1832°F (–200
o
to 1000
o
C).
• If
Slot 1
was chosen, scroll to the desired temperature input (from A to D) and press
[Enter].
The program now returns to the
Channel PROGRAM
menu.
1.3.5
Entering Setup Parameters
The signal limits and response times for the Model XMT868i are specified using the
SET UP
submenu. While following
the programming instructions, refer to Figure 30 on page 9. This submenu includes four options:
•
SIGNL
- set the parameters related to the transducer signal
•
AVRG
- specify the response of the meter to step changes
•
INIT
- initialize all parameters to default values
•
ADVAN
- enable mass flow, edit kinematic viscosity vs. sound speed table, activate K factors, and select transmit
code length.
To enter the
SET UP
submenu, scroll to the
SET UP
option in the
Channel PROGRAM menu and press [Enter].
Remember to record all programmed data in Appendix B,
Data Records
.
Summary of Contents for DigitalFlow XMT868i
Page 2: ......
Page 4: ...ii no content intended for this page...
Page 50: ...Chapter 1 Programming Site Data 42 DigitalFlow XMT868i Programming Manual...
Page 74: ...Chapter 4 Printing Data 2 DigitalFlow XMT868i Programming Manual...
Page 78: ...Chapter 5 Clearing Data 4 DigitalFlow XMT868i Programming Manual...
Page 79: ...DigitalFlow XMT868i Programming Manual 5 Appendix A Menu Maps Appendix A Menu Maps...
Page 80: ...Appendix A Menu Maps 6 DigitalFlow XMT868i Programming Manual...
Page 86: ...Appendix A Menu Maps DigitalFlow XMT868i Programming Manual...
Page 144: ...Appendix D PanaView Menu Maps for the XMT868i 70 DigitalFlow XMT868i Programming Manual...
Page 150: ...Appendix A PanaView Menu Maps DigitalFlow XMT868i Programming Manual 76...
Page 162: ...Warranty 6 AquaTrans AT868 User s Manual no content intended for this page...
Page 163: ......