IG-310-EN version 01; 31/03/2021
23
General instructions
cpg
.0 lite: GIS medium-voltage switchgear,
gas insulated, up to 24 kV,
in accordance with IEC Standard
Installation
6.7. Cable connection
The cables are connected to the bushings with IEC type
reinforced connection connectors (screwable).
Never touch live connectors, not even screened
connectors. Screening does not constitute protection
against direct contact.
When the equipment is in service and a back-up cubicle
is left with voltage in the top busbar and without
cables in the bottom bushings, insulating plugs must
be placed on the bushings or the disconnector must
be placed in earthing position, and locked in this
position with a padlock.
The recommended connectors are detailed below.
Connector Connector
series
Nº
of terminals
Terminal configuration
Rated
current
[A]
Section [mm
2
]
EUROMOLD
Symmetrical
or standard
screening
400TB
1 cable
400TB
630/800
25 - 240
2 cables
440TB+440CP+440TB
1250
185-630
1 cable + Surge arrester
440TB+440PB-10SA
630/800
185-630
440TB
1 cable
440TB
630/1250
185-630
2 cables
440TB+440CP+440TB
1250
185-630
1 cable + Surge arrester
440TB+400PB-10SA
630
185-630
Asymmetrical or
reduced screening
480TB
1 cable
480TB
630/1250
50 - 240
2 cables
480TB+800PB
1250
50 - 240
3 cables
480TB+2X800PB
1250
50 - 240
2 Surge arrester
480TB+800PB+800SA
1250
50 - 240
484TB
1 cable
484TB
630/1250
185 - 630
2 cables
484TB+804PB
1250
185 - 630
3 cables
484TB+2X804PB
1250
185 - 630
2 Surge arrester
484TB+804PB+800SA
1250
185 - 630
NKT Cables
Screened
1 cable
CB 24-630
630
25-300
2 cables
CB 24-630+CC 24-630
1250
2 X 25-300
2 cables
CB 24-630+CC 24-1250/2
1250
25-300 + 300-500
3 cables
CB 24-630+CC 24-630+CC 24-630
1250
3 X 25-300
1 cable
CB 24-1250/2
630/1250
300-500
2 cables
CB 24-1250/2+CC 24-1250/2
1250
2 X 300-500
3 cables
CB 24-1250/2+CC 24-1250/2+CC 24-1250/2
1250
3 X 300-500
1 cable + Surge arrester
CB 24-630+CSA M12
630
25-300
1 cable + Surge arrester
CB 24-1250/2+CSA M12
630/1250
300-500
2 Surge arrester
CB 24-630+CC 24-630+CSA M12
1250
2 X 25-300
TYCO
Screened
1 cable
RSTI-x95x
630
400-800
2 cables
RSTI-x95x + RSTI-CCx95x
1250
2 x 400-800
3 cables
RSTI-x95x+ RSTI-68TP + RSTI-CCx95x
1250
3 x 400-800
Table 6.3.
Recommended connectors