![background image](http://html.mh-extra.com/html/omron/z500-sw17/z500-sw17_setup-manual_743396064.webp)
62
SECTI
ON 4
4-2 Main
tena
nce
Z500
Setup Manual
SECTION 4
Appendix
4-2 Maintenance
In order to ensure performance, carry out the maintenance procedures given below.
NOTICE
• Turn OFF the power and take safety precautions before conducting inspections.
Electric shock can result from attempting safety inspections with the power turned ON.
• Do not use thinners or benzene to clean the Z500.
4-2-1 Cleaning
Optical Filter on Front Panel of Sensor
• Use a blower brush (used to clean camera lenses) to blow large dust particles
from the surface. Do not blow the dust away with your mouth.
• Use a soft cloth (for lenses) with a small amount of alcohol to remove the
remaining dust.
NOTICE
Do not use a scrubbing action when cleaning as scratches on the filter could result in the
Sensor malfunctioning.
Cleaning of Equipment
Remove dirt on equipment by gently wiping with a soft cloth.
4-2-2 Regular Inspections
Inspection point
Details
Tools
required
Power supply
The voltage measured at the power supply terminals
must be 24 VDC + 10 %/ - 10 %.
Circuit tester
Ambient
temperature
The operating ambient temperature inside the
cabinet must be between 0 and 50 ºC
Thermometer
Ambient
humidity
The operating ambient humidity inside the cabinet
must be between 35% and 85%.
Hygrometer
Installation
Each component must be firmly secured.
Each cable connector must be correctly inserted and
locked.
Phillips
screwdriver