3-1-2 Internal Specifications
CHECK
Use a DC power supply with countermeasures against high-voltage spikes (safe extra low-
voltage circuits on the secondary side). Excessively high voltages can result in electric
shock.
Input Specifications
Output Specifications
NOTICE
Do not exceed the maximum load current specified for the Controller.
Note 1:
ON Current/ON Voltage
This refers to the current or voltage values needed to shift from the OFF
→
ON
state.
The ON voltage value is the potential difference between each of the input termi-
nals and COM IN.
Note 2:
OFF Current/OFF Voltage
This refers to the current or voltage values needed to shift from the ON
→
OFF
state.
The OFF voltage value is the potential difference between each of the input ter-
minals and COM IN.
Item
Specification
Model
Z500-MC10E (NPN mode)
Z500-MC15E (PNP mode)
Input voltage
12 to 24 VDC ±10%
ON current (See note 1)
5 to 15 mA
ON voltage (See note 1)
8.8 V max.
OFF current (See note 2)
0.1 mA max.
OFF voltage (See note 2)
4.5 V min.
ON delay
RESET input: 10 ms max.
Other inputs: 0.5 ms max
OFF delay
RESET input: 15 ms max.
Other inputs: 0.7 ms max.
Internal circuits
COM IN
+
Input
terminal
COM IN
Input
terminal
Item
Specification
Model
Z500-MC10E (NPN mode)
Z500-MC15E (PNP mode)
Output voltage
12 to 24 VDC ±10%
Load current
45 mA max.
ON residual voltage
2 V max.
OFF leakage current
0.1 mA max.
Internal circuits
COM OUT
Output terminal
+
Load
COM OUT
Output terminal
Load