Operating Manual

IC:2-60-006-00-00534

1 PHASE PROGRAMMABLE DPM 

AC Volt Meter (1 ) : 

Beta 20

Φ

AC Ammeter (1 ) : 

Beta 10

Φ

Summary of Contents for Beta 10P Series

Page 1: ...Rev B 12 2021 Operating Manual IC 2 60 006 00 00534 1 PHASE PROGRAMMABLE DPM AC Volt Meter 1 Beta 20 Φ AC Ammeter 1 Beta 10 Φ ...

Page 2: ......

Page 3: ... Earth Ground Connections 3 Programming 3 1 Password Protection 3 2 Set Up Screens 3 2 1 Potential Transformer Primary value 3 2 2 Potential Transformer Secondary value 3 2 6 Auto Scrolling 3 2 3 Current Transformer Primary value 3 2 4 Current Transformer Secondary value 3 2 5 Reset of min max values 1 PHASE PROGRAMMABLE DPM AC Volt Meter 1 Beta 20 Φ AC Ammeter 1 Beta 10 Φ Installation Operating I...

Page 4: ...s BETA 20P48x96 5 4 Connection Diagrams for models BETA 10P48x96 Available Models 1 BETA 20P 96X96 with V K K A Y B R R A K V K Y B R R V V K K A Y B R R 14mm Display 2 BETA 10P 96X96 with 14mm Display 3 BETA 20P 96X96 with 20mm Display 4 BETA 10P 96X96 with 20mm Display A K K V Y B R R V 4 BETA 20P 48 X 96 size 4 BETA 10P 48 X 96 size K V K A Y B R R A K V K Y B R R 4 ...

Page 5: ...V Programmable DPM can be configured and Programmed at site for the following PT Primary PT Secondary 1 Scrolls through parameter in upward sequence Display sequence BETA 20P System voltage max Value min value and then back to system Voltage Display sequence BETA 10P system Current max value min value and back to system current These DPMs come with 14mm and 20mm Display options which enables to tak...

Page 6: ... screens These screens may be scrolled through one at a time in incremental order by pressing the key and in decrementing order by pressing key V 2 Measurement Reading Screens Screen 1 System Voltage A Display Screens of PGDV Models V V K K A Y B R R Screen 2 System Voltage Value displayed max Value after Hi flashing on Display V V K K A Y B R R Screen 3 System Voltage min Value Value displayed aft...

Page 7: ...or configuring the BETA 10P and BETA 20P for individual user requirements To access the set up screens press and hold the This will take the User into the Password and Keys Simultaneously Entry Screen Followed Section 3 1 by CodE on Display 3 1 Password Protection Password protection can be enabled to prevent unauthorised access to set up screens By default password protection is not enabled Passwo...

Page 8: ...d Entry V K V K A Y B R R Enter Password first digit entered prompt for Second digit Denotes that decimal point will be flashing Use the key to scroll the value of the second digit from 0 through to 9 the value will wrap from 9 round to 0 Press the key to advance to next digit V K V K A Y B R R V K V K A Y B R R Enter Password second digit entered prompt for Third digit Denotes that decimal point wi...

Page 9: ...se the key to scroll the value of the fourth digit from 0 through to 9 the value will wrap from 9 round to 0 Press the key to advance to next digit V K V K A Y B R R V K V K A Y B R R V K V K A Y B R R Password confirmed Pressing key will advance to the New Password change Password entry stage Pressing the key will advance to the System Type Selection screen See section 3 2 9 ...

Page 10: ...0 0 through to 9 the value will wrap from 9 round to 0 Pressing the key to advance the operation to the next digit and sets the first digit Password entered V K V K A Y B R R V K V K A Y B R R V K V K A Y B R R stage New Change Password first digit entered prompting for second digit Decimal point indicates that this will be flashing Pressing the key will scroll the value of the Second digit from 0 th...

Page 11: ...ourth digit New Change Password second digit entered prompting for third digit decimal point indicates that this will be flashing Pressing the key will scroll the value of the third digit from 0 through to 9 the value will wrap from 9 round to 0 Pressing the key to advance the operation to the next digit and sets the third digit V K V K A Y B R R V K V K A Y B R R Pressing the key to advance the op...

Page 12: ...to Neutral Voltages inclusive of any PT ratio from 60V to 999kV Pressing the key accepts the present value and advances to the Potential Transformer secondary value Edit menu See Section 3 2 2 Pressing the key will enter the Potential transformer Primary Value Multiplier Selection V V K K A Y B R R Initially the multiplier must be selected Pressing the Key will move the decimal point position to t...

Page 13: ...l point position At this stage the decimal point will be ashing When the least significant digit has been set pressing the key will advance to the Potential transformer Primary Value Confirmation screen V V K K A Y B R R Potential Transformer Primary Value Confirmation This screen will only appear following an edit of the Potential Transformer Primary Value followed by ULN If the set value is to be c...

Page 14: ...utomatically goes to value edit Pressing key accepts the present value and then advances to RESET menu section 3 2 5 Pressing the key will enter the PT secondary value edit mode denotes that the decimal point will be flashing Secondary value can be set from 60V to 290VL N back to 0 except Most Significant Digit in which the value will be scrolled from 0 through 2 and back to 0 Pressing will scroll t...

Page 15: ... Edit menu See Section 3 2 4 Pressing the key will shift decimal point position from 100s to 1s digit After 1s position it again shifts Pressing the key accepts the decimal point position and enters into Current the position to 100s digit with annunciation of K It indicates the value in kA V K V K A Y B R R V K V K A Y B R R Transformer Primary value edit significant digit Note the ashing decimal p...

Page 16: ...followed by Ct S on display screen Pressing key accepts the present value and then advances to reset menu section 3 2 5 Pressing the key will scroll between 1 and 5 When desired Current transformer secondary value selected 3 2 4 Current Transformer Secondary Value for BET A 10P models This screen will appear following the edit of PT secondary CT secondary value Confirmation on display pressing will...

Page 17: ...g the parameters it resets the respective parameters as follow None No parameter reset ALL Both min and max values reset Hi max value reset Lo min value reset between the parameters as shown in the screens with pressing the key again V K V K A Y B R R V K V K A Y B R R V K V K A Y B R R V K V K A Y B R R Pressing key scrolls between the screens Pressing selects the displayed parameter and enters t...

Page 18: ... the key will enter into Screen selection Confirmation screen Pressing the key will scroll between Yes and No 3 2 6 Selection of Auto Scrolling or fixed Screen Select Yes for Auto scrolling of parameter display and Select No for fixed display screen V K V K A Y B R R V K V K A Y B R R V K V K A Y B R R Pressing the key set the selected option and Exit set up with entering into measurement mode Auto F...

Page 19: ...gure As the front of the enclosure conforms to IP50 it is protected from water spray from all directions additional protection to the panel may be obtained by the use of an optional panel gasket The terminals at the rear of the product should be protected from liquids The BETA 20P 10P should be mounted in a reasonably stable ambient temperature and 0 where 0 to 50 C Vibration should be kept the op...

Page 20: ... suppression components such as ferrite absorbers line filters etc in the event that RF fields cause problems Note It is good practice to install sensitive electronic instruments that are performing critical functions in EMC enclosures that protect against electrical interference which could cause a disturbance in function 2 Avoid routing leads alongside cables and products that are or could be a so...

Page 21: ...anel Cutout 43 5 0 6 1 81 mm 4 3 Wiring Input connections are made directly to screw type terminals with indirect wire pressure Numbering is clearly marked on the connector Choice of cable should meet local 2 2 regulations Terminal for inputs will accept up to 4mm 12 AWG or 2 5mm 12AWG Standard Note 1 It is recommended to use wire with lug for connection with meter 21 2 For disconnecting the devic...

Page 22: ... are fitted with 1 amp HRC fuse 4 6 Earth Ground Connections For safety reasons panels and accesoriess should be grounded in accordance with local regulations 5 Connection Diagrams 5 1 Connections For BETA 20P 5 2 Connections For BETA 10P SINGLE PHASE 2 WIRE 2 11 13 14 N L O A D L DIGITAL PANEL METER WITH EXTERNAL AUX AUX SUPPLY L N SINGLE PHASE 2 WIRE DIGITAL PANEL METER WITH EXTERNAL AUX 1 3 13 1...

Page 23: ...48X96 model 6 Specifications Inputs BETA 20P Nominal Input Voltage 290V LN Max continuous input voltage 120 of Rated Value Max short duration input voltage 2 x Rated Value 1s application repeated 10 times at 10s intervals System Primary Values 0V to kV 6 999 programmable at site System Secondary Values 0V to 0 V 6 29 programmable at site Overload indication oL 23 Nominal input voltage burden 0 3VA ...

Page 24: ...y Values 1A 5A programmable at site Inputs BETA 10P Overload indication oL If input is greater than 125 of secondary value Nominal Input Current 5A AC Max continuous input current 200 of Rated Value Nominal input Burden 0 2VA approx per phase Max short duration current input 20 x 1s application repeated Rated Value 5 times at 5 min intervals System CT primary values Standard Values 1 to 999 kA Sys...

Page 25: ... Temperature Rated Value 10 0 0 to 50 C 5 120 of Rated Value BETA 10P Current 25 Accuracy Operating Measuring Ranges BETA 20P Voltage 10 120 of Rated Value Frequency 45 65 Hz BETA 10P Current 5 of Rated Value 120 0 5 1 Digit 10 100 of of range BETA 10P Current 0 5 of range 1 Digit 10 100 of BETA 20P Voltage Nominal Value Nominal Value BETA 10P Max 200 input Current 5 200 of Rated Value Optional 0 ...

Page 26: ...between all electrical circuits Dielectric voltage withstand test between circuits and accessible surfaces 26 Error change due to variation of an influence quantity 2 Error allowed for the reference condition applied in the test Auxiliary supply voltage Auxiliary supply frequency Rated Value 5 Rated Value 10 Temperature Coefficient 0 For Rated value range of use 0 50 C 0 025 C 10 120 of Rated Value ...

Page 27: ...8 55mm 68mm Depth 300g Approx 250g Approx Weight 96X96 models 48X96 Models 15g in 3 planes 10 55 Hz 0 15mm amplitude IP 50 IP 20 27 IEC 61010 1 Year 2001 Safety IEC 60529 IP for water dust Environmental conditions Operating temperature Storage temperature Relative humidity Warm up time 0 20 to 70 C 0 30 to 80 C 0 90 RH Non condensing 3 minute minimum ...

Page 28: ...28 NOTE ...

Page 29: ...29 NOTE ...

Page 30: ...memo Invoice This warranty entitles you to bring the meter accessories at your NO TRANSPORTATION CHARGES WILL BE REIMBURSED The warranty is not valid in following cases 1 Warranty card duly signed and stamped and original Cash memo Invoice is not 2 Complete warranty card is not presented to authorised person at the time of repairs sent along with meter accessories 3 Meter accessories is not used a...

Page 31: ...notice transit damage then you must obtain the insurance surveyors report Thank you be final and forward it Scope of supply 1 Side Clamp 2 Connecters 4 User Manual To be filled by authorised dealer Model No Serial Number Date of Purchase Cash Memo Invoice No Dealers Signature Dealer Stamp 5 Warranty Card 6 Test Certificate As per customer requirements 3 Caption Plate ...

Page 32: ...obligations are those in Company standard Conditions of Sale for this product and in no case will Company be liable for any other incidental indirect or consequential damages arising from the use or misuse of the products Sifam Tinsley Instrumentation Ltd Central Buildings Woodland Close Old Woods Trading Estate Torquey Devan England TQ27BB Website www sifamtinsley com uk Contact Number 44 O 1803 ...