SFC Programming Example
Section 1-4
28
-> Transition condition: Trans3/Gate open limit sensor ON (gateopenLimit)
8 If 3 seconds have elapsed since the gate has fully opened, AND if the car has
passed the gate and the vehicle sensor has turned OFF, the transition conditions
are met. The reverse rotation of the gate motor is then turned ON, and the gate
begins to close.
-> Step 4: CloseGate
-> AQ: D (Delay)
-> Action: Active reverse rotation of gate motor
9 When the gate is fully closed, the reverse rotation of the gate motor is turned OFF.
-> Step 4: CloseGate
-> Action: Activate reverse rotation of gate motor
10 When the gate is fully closed, the gate close limit sensor is turned ON, and the
active status is transferred to the next step.
At this point, the reverse rotation of the gate motor is turned OFF.
-> Transition condition: Trans4/Gate close limit sensor ON (gatecloseLimit)
11 The gate returns to the waiting status, and waits for the next car.
Defining Variables for the Unattended Paid Parking Lot
SFC program user variables must be defined for the external I/O devices.
External device
I/O
Variable name
Variable type
Vehicle sensor
Input
carIn
Boolean
Ticket sensor
Input
ticket
Boolean
Gate open limit sensor
Input
gateopenLimit
Boolean
Gate close limit sensor
Input
gatecloseLimit
Boolean
Ticket dispenser
Output
ticketOut
Boolean
Normal operation of gate motor
Output
gateopen
Boolean
Reverse operation of gate
motor
Output
gateClose
Boolean
Note:
It is also possible to specify actual addresses, rather than variables.
Summary of Contents for SYSMAC CX-Programmer 8.1
Page 1: ...Operation Manual SFC Programming SYSMAC WS02 CXPC1 V8 CX Programmer Ver 8 1 Cat No W469 E1 04...
Page 2: ...ii CX Programmer Ver 8 1 WS02 CXPC1 V8 Operation Manual SFC Programming Revised February 2009...
Page 16: ......
Page 56: ...Precautions When Creating SFC Programs Section 1 5 40...
Page 118: ...Monitoring Section 4 5 102...
Page 150: ...Index 134...
Page 152: ...Revision History 136...
Page 153: ......
Page 154: ......