Elements of SFC
Section 2-3
55
Action Execution Timing for Action Qualifiers (AQs)
Step Status
AQ
N
P
P1
P0
L
D
S
SL
SD
DS
Active status
Inactive status
* Executed just twice when the
final scan function is
enabled.
Executed just once when the
final scan function is
disabled.
(When the action is a bit, it is
ON for just one cycle.)
Termination of execution
by the “R” AQ
Executed
Not Executed
*
R
Set Value
Set Value
Set Value
Set Value
Set Value
Set Value
Set Value
Set Value
Set Value
Actions
An action is executed when a step changes to the active status. Actions can be
specified as either of the following:
•
Bit (Boolean variable or actual address)
•
Action program name
When an action is defined as a Boolean variable (bit), the bit is turned ON when the
action is executed, and turned OFF when the action is stopped.
When an action is defined as an action program name, the action program is executed
when the action is executed, and stopped when the action is stopped.
Note: Multiple steps can run the same action program within a single execution of the SFC. Only
simultaneously activated steps are affected by single scan execution.
Boolean Variable or Actual Address (Bit)
An action block can be defined as a Boolean variable or actual address (bit). When the
step becomes active, the Boolean variable or actual address (bit) is turned ON
according to the AQ, and the bit is turned OFF if the action stops.
Summary of Contents for SYSMAC CX-Programmer 8.1
Page 1: ...Operation Manual SFC Programming SYSMAC WS02 CXPC1 V8 CX Programmer Ver 8 1 Cat No W469 E1 04...
Page 2: ...ii CX Programmer Ver 8 1 WS02 CXPC1 V8 Operation Manual SFC Programming Revised February 2009...
Page 16: ......
Page 56: ...Precautions When Creating SFC Programs Section 1 5 40...
Page 118: ...Monitoring Section 4 5 102...
Page 150: ...Index 134...
Page 152: ...Revision History 136...
Page 153: ......
Page 154: ......