Appendices
A - 102
NX-series Digital I/O Unit User’s Manual (W521)
This section lists other objects.
*1. The default value and data range for Number of Entries are as follows.
*2. The meaning of the set values for Input Filter Value Setting is as follows.
*3. The meaning of the set values for Input Filter Mode Setting is as follows.
Other Objects
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5000
Input Filter Setting
00
Number of Entries
*1
*1
USINT
RO
Not
pos-
sible
01
Input Filter Value Setting
3
0 to 11
*2
USINT
RW
Not
pos-
sible
Y
02
Input Filter Mode Setting
0
0/1
*3
USINT
RW
Not
pos-
sible
Y
NX Units
Default value
Data range
NX-MD6121-5/MD6256-5
2
2 (fixed)
Other models
0
0 (fixed)
Set value
Meaning
0
No Filter
1
0.25 ms
2
0.5 ms
3
1 ms
4
2 ms
5
4 ms
6
8 ms
7
16 ms
8
32 ms
9
64 ms
10
128 ms
11
256 ms
Set value
Meaning
0
Enable ON Filter and OFF Filter
1
Enable Only OFF Filter
Summary of Contents for NX-IA3117
Page 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Page 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Page 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Page 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Page 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Page 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Page 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Page 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Page 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...