6 Digital Input Units
6 - 10
NX-series Digital I/O Unit User’s Manual (W521)
Sixteen-point Input Units
*1. The descriptions of Input Filter Value Setting are as follows.
*2. The descriptions of Input Filter Mode Setting are as follows.
Setting name
Description
Default
value
Setting
range
Unit
Index
Subin-
dex
Refer-
ence
Input Filter Value Setting Set the filter time of input
signal.
*1
*1
*1
5000
hex
01 hex
Input Filter Mode Setting Set the operating mode
for the filter.
*2
*2
*2
02 hex
Set
value
Setting description
Default value
Setting range
0
No Filter
3
0 to 11
1
0.25 ms
2
0.5 ms
3
1 ms
4
2 ms
5
4 ms
6
8 ms
7
16 ms
8
32 ms
9
64 ms
10
128 ms
11
256 ms
Set
value
Setting description
Default value
Setting range
0
Enable ON Filter and OFF Filter
0
0/1
1
Enable Only OFF Filter
Summary of Contents for NX-IA3117
Page 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Page 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Page 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Page 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Page 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Page 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Page 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Page 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Page 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...