7 Digital Output Units
NX-series Digital I/O Unit User’s Manual (W521)
7-
4 Fu
nct
ion
7
7-4
-3 Load
S
h
ort-circuit Pr
otection
Restrictions on Use
The load short-circuit protection function only protects internal circuits for a short period.
As shown in the figure above, the load short-circuit protection of this NX Unit is automatically
released when the Tj equals to Tr.
Therefore, unless the cause of short-circuit is removed, ON/OFF operations are repeated in the out-
put.
If the short-circuit is not corrected, output elements deteriorate. If any external load is short-circuited,
immediately turn OFF the applicable output and remove the cause of the short-circuit.
Digital Output Units of PNP outputs
No setting is required.
Target NX Units
Setting Method
Summary of Contents for NX-IA3117
Page 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Page 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Page 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Page 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Page 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Page 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Page 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Page 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Page 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...