A - 87
Appendices
NX-series Digital I/O Unit User’s Manual (W521)
A-5 List of NX Object
s
A
A-
5-2 D
igit
al Input Un
its
*1. The default value and data range for Number of Entries are as follows.
*2. The meaning of the set values for Input Filter Value Setting is as follows.
*3. The meaning of the set values for Input Filter Mode Setting is as follows.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5001
Input Filter Setting
00
Number of Entries
*1
*1
USINT
RO
Not
pos-
sible
01
Input Filter Value Setting
4
0 to 9
*2
USINT
RW
Not
pos-
sible
Y
02
Input Filter Mode Setting
0
0/1
*3
USINT
RW
Not
pos-
sible
Y
NX Units
Default value
Data range
NX-ID3343/ID3443
2
2 (fixed)
Other models
0
0 (fixed)
Set value
Meaning
0
No Filter
1
1
μ
s
2
2
μ
s
3
4
μ
s
4
8
μ
s
5
16
μ
s
6
32
μ
s
7
64
μ
s
8
128
μ
s
9
256
μ
s
Set value
Meaning
0
Enable ON Filter and OFF Filter
1
Enable Only OFF Filter
Summary of Contents for NX-IA3117
Page 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Page 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Page 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Page 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Page 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Page 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Page 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Page 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Page 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...