(c) Relation between OFF current of the DC Input Unit and sensor leakage current
The DC Input Unit cannot detect sensor output OFF unless the following conditions are satisfied:
I
OFF
≥
I
leak
When I
leak
is greater than I
OFF
, connect a bleeder resistor R.
Use the following equation to calculate the bleeder resistance constant of the resistance input.
R
≤
R
IN
× V
OFF
/ (I
leak
× R
IN
- V
OFF
)
Use the following equation to calculate the bleeder resistance constant of the constant current input.
R
≤
(V
OFF
/ I
OFF
) × V
OFF
/ (I
leak
× (V
OFF
/ I
OFF
) - V
OFF
)
For both the resistance input and constant current input, use the following equation to calculate the
rated power of bleeder resistor.
Rated power W of bleeder resistor
≥
(V
CC
- V
R
)
2
/ R × 4 [allowable margin]
The voltages and currents related to the conditions for NPN type sensors are shown in the figure
below.
IN
IOG
IOV
IOG
IOV
V
R
V
CC
R
I
OFF
I
leak
R
IN
V
OFF
Two-wire sensor
DC Input Unit
Communications Coupler Unit or
Additional I/O Power Supply Unit
Summary of Contents for NX-IA3117
Page 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Page 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Page 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Page 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Page 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Page 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Page 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Page 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Page 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...