A - 25
Appendices
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-
1 Dat
a She
et
A
A-
1-3 Analog Output U
nit
s
Analog Output Units (Screwless Clamping Terminal Block, 12 mm
Width)
Unit name
Analog Output Unit (current output type)
Model
NX-DA2203
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8 ter-
minals)
I/O refreshing method
Free-Run refreshing
Indicators
TS indicator
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load resis-
tance
600
Ω
max.
Resolution
1/8000 (full scale)
Overall
accuracy
25
°
C
±0.3% (full scale)
0
to
55
°
C
±0.6% (full scale)
Conversion time
250
μ
s/point
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 M
Ω
min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max., IOG: 0.1 A/termi-
nal max.
NX Unit power con-
sumption
• Connected to a CPU Unit
2.10 W max.
• Connected to a Communications Cou-
pler Unit
1.75 W max.
Current consumption
from I/O power supply
No consumption
Weight
70 g max.
Circuit layout
IOV
AG
IOG
AMP
Output I1+ to I2+
Terminal block
AG: Analog circuit
internal GND
NX bus
connector
(left)
I/O power
I/O power supply
−
I/O power
I/O power supply
−
NX bus
connector
(right)