![background image](http://html1.mh-extra.com/html/omron/nx-ad-series/nx-ad-series_user-manual_743074125.webp)
6 - 9
6 Analog Input Units
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
6-
4 Li
st
of
Se
tti
n
gs
6
*2. The setting range of Ch
Input Moving Average Time depends on the model. The setting range for each
model is as follows.
z
Four-point Input Units
*1. The default value and setting range of Ch
Range Setting depend on the model. The default value and set-
ting range for each NX Unit are as follows.
*2. The setting range of Ch
Input Moving Average Time depends on the model. The setting range for each
model is as follows.
NX Units
Setting range
NX-AD2203/AD2204/AD2603/AD2604
0 to 32000
NX-AD2208/AD2608
0 to 640
Setting name
Description
Default
value
Setting
range
Unit
Index
Subin-
dex
Refer-
ence
Ch1 Enable/Disable
Set to enable or disable
the channel.
FALSE: Disable
TRUE: Enable
TRUE
TRUE or
FALSE
---
5002
hex
01 hex
Ch2 Enable/Disable
TRUE
TRUE or
FALSE
---
02 hex
Ch3 Enable/Disable
TRUE
TRUE or
FALSE
---
03 hex
Ch4 Enable/Disable
TRUE
TRUE or
FALSE
---
04 hex
Ch1 Range Setting
Set the range.
0: 4 to 20 mA
1: 0 to 10 V
2: -10 to +10 V
3: 0 to 5 V
4: 1 to 5 V
5: 0 to 20 mA
*1
*1
---
5003
hex
01 hex
Ch2 Range Setting
*1
*1
---
02 hex
Ch3 Range Setting
*1
*1
---
03 hex
Ch4 Range Setting
*1
*1
---
04 hex
Ch1 Input Moving Aver-
age Time
Set the time to process
moving average.
0
*2
μ
s
5004
hex
01 hex
Ch2 Input Moving Aver-
age Time
0
*2
μ
s
02 hex
Ch3 Input Moving Aver-
age Time
0
*2
μ
s
03 hex
Ch4 Input Moving Aver-
age Time
0
*2
μ
s
04 hex
NX Units
Default value
Setting range
NX-AD3203/AD3204/AD3208
0
0
NX-AD3603/AD3604/AD3608
2
2
NX Units
Setting range
NX-AD3203/AD3204/AD3603/AD3604
0 to 32000
NX-AD3208/3608
0 to 640
Summary of Contents for NX-AD series