7 - 7
7 Analog Output Units
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
7-
4 Li
st of
Sett
ing
s
7
*2. The descriptions of Ch
Hold Value Setting are as follows.
z
Four-point Output Units
Set value
Setting description
0
Hold Last State
1
Low Limit
2
High Limit
3
User Count
4
Zero Count
Setting name
Description
Default
value
Setting
range
Unit
Index
Subin-
dex
Refer-
ence
Ch1 Enable/Disable
Set to enable or disable
the channel.
FALSE: Disable
TRUE: Enable
TRUE
TRUE or
FALSE
---
5010
hex
01 hex
Ch2 Enable/Disable
TRUE
TRUE or
FALSE
---
02 hex
Ch3 Enable/Disable
TRUE
TRUE or
FALSE
---
03 hex
Ch4 Enable/Disable
TRUE
TRUE or
FALSE
---
04 hex
Ch1 Range Setting
Set the range.
0: 4 to 20 mA
1: 0 to 10 V
2: -10 to +10 V
3: 0 to 5 V
4: 1 to 5 V
5: 0 to 20 mA
*1
*1
---
5011
hex
01 hex
Ch2 Range Setting
*1
*1
---
02 hex
Ch3 Range Setting
*1
*1
---
03 hex
Ch4 Range Setting
*1
*1
---
04 hex
Ch1 Hold Value Setting
Set the value to output at
load OFF.
4
0 to 4
*2
---
5012
hex
01 hex
Ch1 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0
-32768 to
32767
---
02 hex
Ch2 Hold Value Setting
Set the value to output at
load OFF.
4
0 to 4
*2
---
03 hex
Ch2 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0
-32768 to
32767
---
04 hex
Ch3 Hold Value Setting
Set the value to output at
load OFF.
4
0 to 4
*2
---
5012
hex
05 hex
Ch3 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0
-32768 to
32767
---
06 hex
Ch4 Hold Value Setting
Set the value to output at
load OFF.
4
0 to 4
*2
---
07 hex
Ch4 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0
-32768 to
32767
---
08 hex
Summary of Contents for NX-AD series