8 Troubleshooting
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
8-3 Ch
eckin
g
fo
r Er
ro
rs and
T
rou
blesh
oot
ing
on
the
Supp
ort So
ftwar
e
8
8-3
-4 Meaning of Er
ror
Event name
Analog Unit Calibration Parameter Error
Event code
10400000 hex
Meaning
An error occurred for the calibration data in the Analog Unit.
Source
Depends on where the Support
Software is connected and the
system configuration.
Source details
NX Unit
Detection
timing
When power is
turned ON to
the NX Unit
Error
attributes
Level
Minor fault
Log category
System
Recovery
For the NX bus of CPU Units
When Fail-soft Operation Is Set to
Stop
Restart the NX Unit and then reset the error in the NX Bus Function
Module.
When Fail-soft Operation Is Set to
Fail-soft
Restart the NX Unit.
For Communications Coupler Units
When Fail-soft Operation Is Set to
Stop
Restart the NX Unit.
If the errors are detected in the Controller, reset all of the errors in the
Controller.
When Fail-soft Operation Is Set to
Fail-soft
Restart the NX Unit.
Effects
User program
Continues.
Operation
I/O refreshing for the NX Unit stops.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power supply to the Analog
Unit was turned OFF or Support
Software communications were
disconnected while writing the cal-
ibration values to the Analog Unit.
Write the calibration values to the
Analog Unit again.
Do not turn OFF the power supply
to the Analog Unit or disconnect
Support Software communications
while writing the calibration values
to the Analog Unit.
Attached
information
None
Precautions/
Remarks
None