Appendices
A - 52
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
*1. The default value and data range for Number of Entries are as follows.
*2. The default value and data range for Ch
Range Setting are as follows.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5011
---
Output Range Setting
---
---
---
---
---
---
---
00
Number of Entries
*1
*1
---
USINT
RO
Not
pos-
sible
---
01
Ch1 Range Setting
*2
*2
---
UINT
RW
Not
pos-
sible
Y
02
Ch2 Range Setting
---
UINT
RW
Not
pos-
sible
Y
03
Ch3 Range Setting
---
UINT
RW
Not
pos-
sible
Y
04
Ch4 Range Setting
---
UINT
RW
Not
pos-
sible
Y
NX Units
Default value
Data range
NX-DA2203/DA2205/DA2603/
DA2605
2
2
NX-DA3203/DA3205/DA3603/
DA3605
4
4
Other models
0
0
NX Units
Set
value
Meaning
Default value
Data range
NX-DA2203/DA2205/DA3203/
DA3205
0
4 to 20 mA
0
0
1
0 to 10 V
2
-10 to +10 V
3
0 to 5 V
4
1 to 5 V
5
0 to 20 mA
NX-DA2603/DA2605/DA3603/
DA3605
0
4 to 20 mA
2
2
1
0 to 10 V
2
-10 to +10 V
3
0 to 5 V
4
1 to 5 V
5
0 to 20 mA
Summary of Contents for NX-AD series