4 Installation and Wiring
4 - 20
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
z
Securing Wires
It is necessary to secure wires to the screwless clamping terminal block depending on the wire types
that are used or the current flows on the wires.
The following table gives the necessity for securing wires.
Use the following procedure to secure the wires.
1
Prepare a cable tie.
A cable tie can be used with a width of 4 mm or less and a thickness of 1.5 mm or less.
Select a cable tie correctly for the operating environment.
2
Pass a cable tie through the hole for securing wires on the bottom of the screwless clamping ter-
minal block.
Terminals
Wire type
Ferrule
Twisted wires
Solid wire
Classifica-
tion
Current
capacity
Plated
Unplated
Plated
Unplated
All terminals
except
ground
terminals
2 A max.
No
No
No
No
No
Greater than
2 A and 4 A or
less
Not Possible
Yes
Not Possible
Greater than
4 A
Yes
Not Possible
Ground
terminals
---
No
No
No
No
1.5 mm or less
4.0 mm or less
Hole for securing wires
Cable tie