![background image](http://html1.mh-extra.com/html/omron/nx-ad-series/nx-ad-series_user-manual_743074265.webp)
A - 45
Appendices
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-
3 List
of
NX Object
s
A
A-
3-2 Analog Inpu
t Unit
s
*1. The default value and data range for Number of Entries are as follows.
*2. The setting range of Ch
Input Moving Average Time depends on the model. The input moving average time data range
for each type is as follows.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5004
---
Input Moving Average
Time
---
---
---
---
---
---
---
00
Number of Entries
*1
*1
---
USINT
RO
Not
pos-
sible
---
01
Ch1 Input Moving Average
Time
0
*2
μ
s
UINT
RW
Not
pos-
sible
Y
02
Ch2 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
03
Ch3 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
04
Ch4 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
05
Ch5 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
06
Ch6 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
07
Ch7 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
08
Ch8 Input Moving Average
Time
0
UINT
RW
Not
pos-
sible
Y
NX Units
Default value
Data range
NX-AD2203/AD2204/AD2208/
AD2603/AD2604/AD2608
2
2
NX-AD3203/AD3204/AD3208/
AD3603/AD3604/AD3608
4
4
NX-AD4203/AD4204/AD4208/
AD4603/AD4604/AD4608
8
8
Other models
0
0
NX Units
Data range
NX-AD2203/AD2204/AD2603/
AD2604/AD3203/AD3204/
AD3603/AD3604/AD4203/
AD4204/AD4603/AD4604
0 to 32000
NX-AD2208/AD2608/AD3208/
AD3608/AD4208/AD4608
0 to 640