Appendices
A - 2
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-1 Data Sheet
This section provides the specifications of individual Analog Input Units and Analog Output Units.
A-1-1
Model List
Analog Input Units (Screwless Clamping Terminal Block, 12 mm
Width)
Model
Num
ber
of
poin
ts
Input range
Resolu-
tion
Input
method
I/O refresh-
ing method
Conver-
sion time
Reference
NX-AD2203
2
point
s
4 to 20 mA
1/8000
Sin-
gle-ende
d
Free-Run
refreshing
250
μ
s/point
NX-AD2204
Differen-
tial
NX-AD2208
1/30000
Switching
Synchronous
I/O refreshing
and Free-Run
refreshing
10
μ
s/point
NX-AD2603
-10 to +10 V
1/8000
Sin-
gle-ende
d
Free-Run
refreshing
250
μ
s/point
NX-AD2604
Differen-
tial
NX-AD2608
1/30000
Switching
Synchronous
I/O refreshing
and Free-Run
refreshing
10
μ
s/point
NX-AD3203
4
point
s
4 to 20 mA
1/8000
Sin-
gle-ende
d
Free-Run
refreshing
250
μ
s/point
NX-AD3204
Differen-
tial
NX-AD3208
1/30000
Switching
Synchronous
I/O refreshing
and Free-Run
refreshing
10
μ
s/point
NX-AD3603
-10 to +10 V
1/8000
Sin-
gle-ende
d
Free-Run
refreshing
250
μ
s/point
NX-AD3604
Differen-
tial
NX-AD3608
1/30000
Switching
Synchronous
I/O refreshing
and Free-Run
refreshing
10
μ
s/point
Summary of Contents for NX-AD series