3 Operation
3 - 22
Grid Connect Photovoltaic Inverter KP100L-OD-
USER’S MANUAL
Details of sequences during the Auto Test
Items
Sequences during the auto test
LCD
(1)
The Auto
Test of
OV [L1]
(1-1)The inverter turns on the inside Grid-connected
relay
(1-2)Detect level of OV [L1] is decreased at the point of
0.5V/s
(1-3)Grid-connected relays are disconnected, when OV
[L1] detect level keeps below the grid voltage for
more than OV [L1] detect time
(1-4)Detect level and detect time of OV [L1] detected in
(1-3) are shown. (Display for ten seconds.)
(2)
The Auto
Test of
OV [L2]
(2-1)The inverter turns on the inside Grid-connected
relay
(2-2)Detect level of OV [L2] is decreased at the point of
0.5V/s
(2-3)Grid-connected relays are disconnected, when OV
[L2] detect level keeps below the grid voltage for
more than OV [L2] detect time
(2-4)Detect level and detect time of OV [L2] detected in
(2-3) are shown. (Display for ten seconds.)
The grid voltage of L1
[e.g.] in the case of 230.03V
Setup level of OV [L1]
[e.g.] in the case of 270.00V
AutoTest:OV [L1]
230.03V / 270.00V
AutoTest:OV [L1]
230.05V / 110ms
Detect level of OV [L1]
[e.g.] in the case of 230.05V
Detect time of OV [L1]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of OV [L2]
Result of OV phase L1
The grid voltage of L2
[e.g.] in the case of 230.03V
Setup level of OV [L2]
[e.g.] in the case of 270.00V
AutoTest:OV [L2]
230.03V / 270.00V
AutoTest:OV [L2]
230.05V / 110ms
Detect level of OV [L2]
[e.g.] in the case of 230.05V
Detect time of OV [L2]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of OV [L3]
Result of OV phase L2
Summary of Contents for KP100L-OD - 12-2010
Page 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...