3 - 23
3 Operation
Grid Connect Photovoltaic Inverter KP100L-OD-
USER’S MANUAL
3-6 Setting
in Particu
lar Co
untries
3
9
(3)
The Auto
Test of
OV [L3]
(3-1)The inverter turns on the inside Grid-connected
relay
(3-2)Detect level of OV [L3] is decreased at the point of
0.5V/s
(3-3)Grid-connected relays are disconnected, when OV
[L3] detect level keeps below the grid voltage for
more than OV [L3] detect time
(3-4)Detect level and detect time of OV [L3] detected in
(3-3) are shown. (Display for ten seconds.)
(4)
The Auto
Test of
UV [L1]
(4-1)The inverter turns on the inside Grid-connected
relay
(4-2)Detect level of UV [L1] is increased at the point of
0.5V/s
(4-3)Grid-connected relays are disconnected, when UV
[L1] detect level keeps above the grid voltage for
more than UV [L1] detect time
(4-4)Detect level and detect time of UV [L1] detected in
(4-3) are shown. (Display for ten seconds.)
Items
Sequences during the auto test
LCD
The grid voltage of L3
[e.g.] in the case of 230.03V
Setup level of OV [L3]
[e.g.] in the case of 270.00V
AutoTest:OV [L3]
230.03V / 270.00V
AutoTest:OV [L3]
230.05V / 110ms
Detect level of OV [L3]
[e.g.] in the case of 230.05V
Detect time of OV [L3]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of UV [L1]
Result of OV phase L3
The grid voltage of L1
[e.g.] in the case of 230.02V
Setup level of UV [L1]
[e.g.] in the case of 184.00V
AutoTest:UV [L1]
230.02V / 184.00V
AutoTest:UV [L1]
230.04V / 110ms
Detect level of UV [L1]
[e.g.] in the case of 230.04V
Detect time of UV [L1]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of UV [L2]
Result of UV phase L1
Summary of Contents for KP100L-OD - 12-2010
Page 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...