4 - 7
4 Maintenance Operations
Grid Connect Photovoltaic Inverter KP100L-OD-
USER’S MANUAL
4-2 R
emed
y fo
r err
o
rs
4
9
E1-8: Under voltage instantly (Grid)
E2-1: Over voltage (DC)
E2-3: Ground I Fault
Situation
The grid voltage drops below 110V.
Possible Cause
1. AC connection is not correct.
2. Grid condition is weak or unstable.
3. Other high-power consumption device is affecting the grid system.
4. Inverter is abnormal.
Remedy for User
1. If this problem occurs seldom (such as 1 time a day), no action is necessary.
Operation will restart automatically when the grid voltage returns to normal.
If the problem occurs frequently, do the actions below.
2. Find the device with high power consumption near your AC system.
3. Consult your utility power supplier, understand the grid conditions.
4. Ask help of your installer.
Remedy for Professional
1. Check the system connection including polarities and security first.
2. Find the devices with high power consumption near the AC system.
3. Consult the utility power supplier, understand the grid conditions.
4. Use Inverter software to monitor the frequency and voltage.
5. If the situation is not improved, please replace the Inverter.
Situation
The detected PV voltage is higher than specification.
Possible Cause
1. The PV array voltage is too high.
2. Inverter is abnormal.
Remedy for User
1. If the fault continues, contact the store from which you purchased the product or your
installer.
Remedy for Professional
1. Check the open PV voltage, and see if it is more than or too close to specification.
2. If PV voltage is much less than specification and the problem still occurs, please
replace the Inverter.
Situation
The fault current detected by the Inverter is higher than threshold.
Possible Cause
1. Obstacle, humidity or water exits between AC LINE and/or NEUTRAL to earth
ground.
2. Obstacle, humidity or water exits between AC LINE and/or NEUTRAL to earth ground
in the junction box.
3. The Insulation of AC wires is broken that could be bit by rat or any animals.
4. Inverter is abnormal.
Remedy for User
1. Disconnect AC connection of Inverter by opening AC switch.
2. Check the AC junction box and wiring of system. Clear obstacle ONLY IN SAFE
CONDITIONS
3. Reconnect AC connection, check the status of Inverter.
4. If the problem persists, contact the store from which you purchased the product or
your installer.
Remedy for Professional
1. Disconnect AC side of Inverter by opening AC switch.
2. Disconnect the DC side from the Inverter.
3. Check both the AC and DC wiring and insulation.
4. Reconnect AC connection, check the status of Inverter
5. If the problem persists, please replace the Inverter.
Summary of Contents for KP100L-OD - 12-2010
Page 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...