3 - 13
3 Operation
Grid Connect Photovoltaic Inverter KP100L-OD-
USER’S MANUAL
3-5 Mo
de Select
ion
Disp
lay
3
9
*1 When communication protocol is set to Modbus , "Communication Unit Number 00" is communication unit number of
broadcast. Thus, set "Communication Unit Number" not include 00 when you do the communications other than the
Broadcast with Modbus.
*2 In the case of the Modbus setting, the silent interval is not included in the RS-485 Communication Send wait the time.
Item
display
Set Value
Mean
Initial
value
Unit
[1]
Setup of Language
Language
ENG
English
ENG -
ITA
Italian
ESP
Spanish
GER
German
FRA
French
[2]
Communication protocol
[Compoway/F, Modbus]
COM_Prot
Auto
Auto distinction
Auto
-
Compoway
Compoway/F
Modbus
Modbus
[3]
Communication Unit
Number (*1)
[Compoway/F, Modbus]
COM_Unit
0 to 99
0
-
[4]
Communication Baud
rate (RS-232C)
[Compoway/F]
COM_232C
4800
9600
bps
9600
19200
[5]
Communication Baud
rate (RS-485)
[Compoway/F, Modbus]
COM_485
4800
19200 bps
9600
19200
[6]
Communication Parity
[Modbus]
COM_Pari
None
No parity
Even
-
Even
Even parity
Odd
Odd parity
[7]
Communication Stop bit
[Modbus]
COM_Stop
1
1
bit
2
[8]
RS-485 Communication
Send wait time (*2)
[Compoway/F, Modbus]
COM_Wait
0 to 99
0
ms
[9]
Change of parameter
level (GER or ITA)
PARAM_LV
0,1
0
-
[10] Setup level for control of
the grid voltage
increasing
PF_LV
0.0 to
30.0 OV setup level - this setup level
0.0
V
[11]
Setup of Output Signal 1
(Relay outputs:
AUX_OUT1)
OutSig1
MODE1
Breakdown output mode
MODE1
-
MODE2
Output mode of PV system's fault
MODE3
Output mode of grid system's fault
MODE4
Output mode of all errors
MODE5
Output mode of all errors (except grid
system's fault)
[12] Setup of Output Signal 2
(Relay outputs:
AUX_OUT2)
OutSig2
MODE1
synchronization mode with grid relay
MODE1
-
MODE2
synchronization mode with
communication
[13] Setup of Input Signal
(PHC INPUT: AUX_IN)
InputSig
MODE1
Operation stop mode
MODE1
-
MODE2
Gate block mode
[14] Error Reset
ErrReset
-
-
-
[15] Clear of Total Periodic
Energy
TotalClr
-
-
-
[16] Auto Test (ITA only)
AutoTest
-
-
-
Summary of Contents for KP100L-OD - 12-2010
Page 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Page 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Page 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...