0
For the RS-422 (E5AF-A02) and RS-485 (E5AF-A03) Models, designate the
E5AF located at both ends of the transmission line as an terminator by set-
ting the terminator switch of that Controller to ON. (Terminator designation is
not required for the RS-232C Models.)
Terminator switches
Communications
connector
SW601 and SW602 are factory set to OFF. SW601 and SW602 of Controllers
other than the terminator must be OFF.
OFF
ON
SW602 SW601
Terminator
SW602
SW601
RS-422 designation
ON
ON
RS-485 designation
There is no SW602.
ON
Caution If a wrong Controller is designated as the terminator, the operating current
will increase, thus causing the Fuzzy Temperature Controller to malfunction.
Terminator Designation
Terminator Switches
Section 3--2
Summary of Contents for E5AF
Page 1: ...E5AF E5EF Fuzzy Temperature Controller Operation Manual Produced July 1992 ...
Page 2: ... ...
Page 4: ... ...
Page 5: ... 0 1 2 3 0 3 3 4 5 6 7 1 8 6 5 9 6 5 9 8 ...
Page 6: ... 0 1 2 ...
Page 8: ... 8 2 8 ...
Page 10: ... The Heater Burnout Detection Models are shown below E5AF AH E5EF AH Section 1 2 ...
Page 11: ... 8 2 8 1 8 2 8 8 ...
Page 17: ... 8 2 8 8 8 8 2 8 8 5 0 1 2 3 0 3 3 4 5 5 5 ...
Page 47: ... 8 2 8 8 1 8 5 6 7 8 1 8 0 6 5 9 6 5 2 6 5 2 0 6 6 5 9 5 8 ...
Page 71: ... 8 2 8 8 8 8 5 8 ...
Page 78: ... 0 1 0 2 3 1 1 4 0 1 1 1 1 5 5 6378 6 78 5 0 2 10 0 00 0 0 9 4 9 1 3 04 1 0 0 0 2 ...
Page 79: ... 1 6 8 6 8 6 58 0 1 4 0 0 2 1 1 1 1 14 4 4 4 1 1 1 9 1 1 0 0 1 ...
Page 80: ... 14 6 8 14 4 1 4 5 0 1 0 1 0 ...