3--6
Header Codes
The following table shows the header codes for each Model. The codes are
accompanied by their function names. The table also indicate whether each
of the functions can be operated in the Remote mode and the Local mode.
For further details, check the reference section in the last column.
Header code
Name
Remote mode
Local mode
Remarks
Reference
section
ME
MA
Backup mode
RAM write mode selection
Yes
------
(See Note 1)
3--7
MW
RAM data all save
Yes
------
(See Note 1)
3--8
MB
Remote/Local mode select
Yes
Yes
(See Note 3)
3--9
WS
W%
WI
WB
WN
WV
Main setting write
Alarm temperature write
Input shift value write
Proportional band write
Integral time write
Derivative time write
Yes
------
(See Note 1)
3--10
WW
Heater burnout alarm
temperature write
Yes
------
(See Note 1
and 2)
3--10
Wj
Fuzzy strength write
Yes
------
(See Note 1)
3--10
Wk
Fuzzy scale 1 write
Yes
------
3--10
W
Fuzzy scale 2 write
Yes
------
3--10
RS
R%
RI
RB
RN
RV
RO
Main setting read
Alarm temperature read
Input shift value read
Proportional band read
Integral time read
Derivative time read
Output value read
Yes
Yes
------
3--11
RW
Heater burnout alarm
temperature read
Yes
Yes
(See Note 2)
3--11
Rj
Fuzzy strength read
Yes
Yes
------
3--11
Rk
Fuzzy scale 1 read
Yes
Yes
3--11
R
Fuzzy scale 2 read
Yes
Yes
3--11
RL
Setting limit read
Yes
Yes
------
3--12
RX
Process temperature read
Yes
Yes
------
3--13
RZ
Heater current read
Yes
Yes
(See Note 2)
3--14
RU
Initial status read
Yes
Yes
------
3--15
AS
Auto-tuning start
Yes
------
------
3--16
AP
Auto-tuning stop
Yes
------
------
3--17
IC
Undefined error
Yes
Yes
Response to an
undefined
header code.
3--18
Note 1. Write commands are not valid in the local mode or during auto-tuning. If
attempted, an end code “0D” (command cannot be executed) reply will be
received.
2. These header codes are available when using the E5AF/E5EF-AH
=
and
E5EF-BAH.
3. This header code is available when using the E5EF-AH
=
and E5EF-BAH.
!
Section 3--6
Summary of Contents for E5AF
Page 1: ...E5AF E5EF Fuzzy Temperature Controller Operation Manual Produced July 1992 ...
Page 2: ... ...
Page 4: ... ...
Page 5: ... 0 1 2 3 0 3 3 4 5 6 7 1 8 6 5 9 6 5 9 8 ...
Page 6: ... 0 1 2 ...
Page 8: ... 8 2 8 ...
Page 10: ... The Heater Burnout Detection Models are shown below E5AF AH E5EF AH Section 1 2 ...
Page 11: ... 8 2 8 1 8 2 8 8 ...
Page 17: ... 8 2 8 8 8 8 2 8 8 5 0 1 2 3 0 3 3 4 5 5 5 ...
Page 47: ... 8 2 8 8 1 8 5 6 7 8 1 8 0 6 5 9 6 5 2 6 5 2 0 6 6 5 9 5 8 ...
Page 71: ... 8 2 8 8 8 8 5 8 ...
Page 78: ... 0 1 0 2 3 1 1 4 0 1 1 1 1 5 5 6378 6 78 5 0 2 10 0 00 0 0 9 4 9 1 3 04 1 0 0 0 2 ...
Page 79: ... 1 6 8 6 8 6 58 0 1 4 0 0 2 1 1 1 1 14 4 4 4 1 1 1 9 1 1 0 0 1 ...
Page 80: ... 14 6 8 14 4 1 4 5 0 1 0 1 0 ...