,(
2. Control Output
0%
100%
20 mA
4 mA
Output
Normal output
0%
100%
Output
Reverse output
20 mA
4 mA
Output Data vs. Output Current
Output value
Process temperature
Output amount
Normal
Reverse
Normal
Reverse
20 mA to 4 mA
to
to
100.0 to 0.0%
0.0 to 100.0%
Note 1. The upper limit of the set value is expressed by
8
and the lower limit of
it is expressed by
.
2. In the case of A/D error, memory error, or abnormal input, 1 mA (safety
side) is output in the same manner as the Electrical Current Output Unit.
3. If the process temperature exceeds either edge of the set limit, the trans-
feroutput will rither be 4 mA or 20 mA.
(
Section 5--2
Summary of Contents for E5AF
Page 1: ...E5AF E5EF Fuzzy Temperature Controller Operation Manual Produced July 1992 ...
Page 2: ... ...
Page 4: ... ...
Page 5: ... 0 1 2 3 0 3 3 4 5 6 7 1 8 6 5 9 6 5 9 8 ...
Page 6: ... 0 1 2 ...
Page 8: ... 8 2 8 ...
Page 10: ... The Heater Burnout Detection Models are shown below E5AF AH E5EF AH Section 1 2 ...
Page 11: ... 8 2 8 1 8 2 8 8 ...
Page 17: ... 8 2 8 8 8 8 2 8 8 5 0 1 2 3 0 3 3 4 5 5 5 ...
Page 47: ... 8 2 8 8 1 8 5 6 7 8 1 8 0 6 5 9 6 5 2 6 5 2 0 6 6 5 9 5 8 ...
Page 71: ... 8 2 8 8 8 8 5 8 ...
Page 78: ... 0 1 0 2 3 1 1 4 0 1 1 1 1 5 5 6378 6 78 5 0 2 10 0 00 0 0 9 4 9 1 3 04 1 0 0 0 2 ...
Page 79: ... 1 6 8 6 8 6 58 0 1 4 0 0 2 1 1 1 1 14 4 4 4 1 1 1 9 1 1 0 0 1 ...
Page 80: ... 14 6 8 14 4 1 4 5 0 1 0 1 0 ...