108
Errors and Troubleshooting
Section 6-1
SS indicator lit red.
One or more of the connected Sen-
sors is faulty.
Replace the Sensors.
Determine which Sensors are faulty by checking the num-
ber of Sensors able to communicate.
One or more of the connected Sen-
sors has been disconnected.
Connect the Sensors correctly.
Determine the Sensor error location by checking the num-
ber of Sensors able to communicate.
The number of registered Sensors is
incorrect.
Register the number of Sensors correctly.
Pin 3 of the DIP switch is incorrectly
set.
Set DIP switch pin 3 correctly.
Pin 3 OFF: Set using rotary switch.
Pin 3 ON: Set using CompoWay/F message communica-
tions.
One or more of the connected Fiber
Amplifier Units is from an unsupported
lot number.
Replace the unsupported Fiber Amplifier Units with those
from supported lot numbers. (Refer to 1-3-3 Supported
Fiber Amplifier Units.)
The number of Sensors connected is
more than the permissible amount.
Connect a number of Sensors that is within the limit.
The reset switch was pressed while
the Mobile Console was connected.
Temporarily disconnect the Mobile Console.
The Unit is faulty.
Replace the Unit.
Indicator status
Probable cause
Remedy
Summary of Contents for E3X-CIF11
Page 3: ...iv...
Page 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Page 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Page 107: ...96 CompoWay F Message Communications Section 4 5...
Page 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Page 133: ...122 DeviceNet Connection Settings Appendix C...
Page 135: ...124 DeviceNet Device Profile Appendix D...
Page 137: ...126 Revision History...