Operating Procedure for CompoBus/S Communication Unit
Section 3-3
3-3
Operating Procedure for CompoBus/S Communication
Unit
Step
Item
Details
1
Mount the Communication Unit to
the DIN Track.
Mount the Unit to the DIN Track. After mounting the Fiber Amplifier Units to
the DIN Track, connect the Units to each other.
Note: To remove the Units from the DIN Track, first slide the Units apart to
disconnect them, and then remove the Units from the DIN Track.
2
Connect the Fiber Amplifier Units
to the Communication Unit.
Connect the Communication Unit to the Fiber Amplifier Units by sliding the
Communication Unit until the clips on the end are aligned and a “click” sound
is heard.
3
Set the Sensors to RUN mode
Set the mode switches to RUN mode.
4
Connect the CompoBus/S commu-
nications connector.
The DC power supply to the Communication Unit and all Fiber Amplifier Units
connected to it is supplied from the CompoBus/S communications power sup-
ply (BS+, BS–).
5
Set the rotary switches.
Upper
switch
Sets the CompoBus/S node address (0 to F).
Lower
switch
Sets the number of Sensors connected to the Unit (1 to 14).
6
Set the DIP switch
Pin 1
Maximum number of Sensors connected Allocated node address
OFF
6
One node in IN Area
ON
14
Two nodes in IN Area
Pin 2
CompoBus/S communications mode
OFF
High-speed mode
ON
Long-distance mode
7
Turn ON the DC power supply
(BS+, BS– CompoBus/S communi-
cations power supply).
Disconnect the E3X-MC11 Mobile Console before turning ON the DC power
supply.
8
Check the indicators.
PWR
Communications power supply is ON when the PWR indicator is lit
green.
COMM
CompoBus/S communications are normal when the COMM indica-
tor is lit yellow.
ERR
Operation is normal when the ERR indicator is not lit (no Compo-
Bus/S communications error).
U.ERR
Operation is normal when the U.ERR indicator is not lit (no Unit
error).
SS
Sensors are communicating when the SS indicator is lit green.
9
Start communi-
cations
Remote I/O
communications
Change the PLC to RUN mode.
Summary of Contents for E3X-CIF11
Page 3: ...iv...
Page 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Page 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Page 107: ...96 CompoWay F Message Communications Section 4 5...
Page 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Page 133: ...122 DeviceNet Connection Settings Appendix C...
Page 135: ...124 DeviceNet Device Profile Appendix D...
Page 137: ...126 Revision History...