Overview of CompoBus/S Communications Model
Section 3-1
3-1-3
Using CompoBus/S Remote I/O Communications: Example
The following example is for monitoring the ON/OFF output status of Fiber
Amplifier Unit number 1, with DIP switch pin 1 OFF, E3X-SRT21 CompoBus/S
node address 00, and CompoBus/S Master Unit Special I/O Unit number 0.
The IN Area starts at CIO 2000 and runs through the rightmost byte (bits 00 to
07) of CIO 2004 (word n + 4) in the IN Area. The eight bits of the Communica-
tion Unit slave 00 are allocated bits 00 to 07 of CIO 2004.
Communications
method
Communications mode
Allocated
words
Communications data
Number of
Sensors
Remote I/O com-
munications (func-
tions as
CompoBus/S
slave)
Up to 6 Sensors
High-speed
communications
One node
in IN Area
Sends following data to master:
ON/OFF output signals for up to 6
Sensors
6 max.
Long-distance
communications
Up to 14 Sensors High-speed
communications
Two nodes
in IN Area
Sends following data to master:
ON/OFF output signals for up to 14
Sensors
14 max.
Long-distance
communications
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
CIO 2004
Node address 00
Sensor ON/OFF
output status for
Unit 1
Bits
E3X-SRT21
node address 00
Reflected in
IN Area
Fiber Sensors
Unit 1 for which
ON/OFF data is
being monitored.
CompoBus/S
CS1 CPU Unit
IN Area
C200HW-SRM21-V1 CompoBus/S Unit
remote I/O communications
IN Area (When Special I/O Unit unit number of CompoBus/S Master Unit is 0)
Summary of Contents for E3X-CIF11
Page 3: ...iv...
Page 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Page 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Page 107: ...96 CompoWay F Message Communications Section 4 5...
Page 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Page 133: ...122 DeviceNet Connection Settings Appendix C...
Page 135: ...124 DeviceNet Device Profile Appendix D...
Page 137: ...126 Revision History...