33
Explicit Message Communications
Section 2-6
This command cannot be used if one or more E39-TM1 Terminal Block Units
is connected.
Read Basic Settings
Reads the basic settings of the Sensor for the unit number specified in the
instance ID. The data contents are as follows:
Read Timer Settings
Reads the OFF-delay, ON-delay, and one-shot timers of the Sensor for the
unit number specified in the instance ID. The data is given as a 2-byte (4-digit)
hexadecimal value. The value is given in ms.
Bit
Contents
00
Display Contents:
0: Digital incident level
1: Digital percentage
2: Analog incident level
01
02
Display Orientation:
0: Standard
1: Reversed
03
Hold Setting:
0: OFF
2: Peak
3: Bottom
04
05
Flashing Setting:
0: OFF
1: ON
06
Sensing Setting:
0: Standard
2: Super long-distance
3: Super high-speed
07
08
Timer Mode:
1: OFF-delay
2: ON-delay
3: One-shot
09
10
Number of Display Digits:
0: 4 digits
1: 3 digits
2: 2 digits
3: 1 digit
4: 0 digits
11
12
13
Always 0.
14
Teaching during RUN
0: OFF
1: ON
15
Eco Mode
0: OFF
1: ON
Summary of Contents for E3X-CIF11
Page 3: ...iv...
Page 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Page 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Page 107: ...96 CompoWay F Message Communications Section 4 5...
Page 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Page 133: ...122 DeviceNet Connection Settings Appendix C...
Page 135: ...124 DeviceNet Device Profile Appendix D...
Page 137: ...126 Revision History...