![background image](http://html1.mh-extra.com/html/omron/cxone-ald-v4-10-2010/cxone-ald-v4-10-2010_operation-manual_743059133.webp)
117
Segment Program 3 (Block Model 158)
Section 6-19
13: ADV Button
When touched, 1 is set in the write address for tag ITEM S4 (ITEM 018: Step
command). Tag ITEM S4 (ITEM 018) is displayed in yellow when the value is
0, and in red when the value is 1.
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address for tag ITEM S4 (ITEM 018) is set as the write
address, and the read address for tag ITEM S4 (ITEM 018) is set as display
address 1. The label displays “ADV” in the rough font.
14: START Button
When touched, 1 is set in the write address for tag ITEM S1 (ITEM 013: Run/
stop command). Tag ITEM S1 (ITEM 013) is referenced and the color is dis-
played according to the following table.
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “START” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S1 (ITEM 013).
$B32766=1;
WRITECMEM ([S1],$B32766,1) ;
15: STOP Button
When touched, 0 is set in the write address for tag ITEM S1 (ITEM 013: Run/
stop command). Tag ITEM S1 (ITEM 013) is referenced and the color is dis-
played according to the following table.
The button is built as a momentary ON/OFF Button with a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “STOP” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 0 is written to the write address of tag ITEM S1 (ITEM 013).
$B32766=0;
WRITECMEM ([S1],$B32766,1) ;
S1 (ITEM 013) value
Color
0
Yellow
1
Red
S1 (ITEM 013) value
Color
0
Red
1
Yellow
Summary of Contents for CXONE-ALD-V4 - 10-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 22: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 28: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 29: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 40: ...24 Merging Projects Section 4 2...
Page 142: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 144: ...128 Revision History...