4-3
Section
CIO Area Allocations
52
Status of UDP/TCP Sockets 1 to 8 (Ethernet Unit to CPU Unit)
Opening Flag
Receiving Flag
Sending Flag
Closing Flag
Results Storage Error Flag
TCP/UDP Open Flag
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
n+1 to n+16
Bit
Flag
Status
Manipulated
by
Unit operation
Reference
0
Opening Flag
ON
Unit
ON during open processing. (Turns ON when
open request is received.)
Section 6
Socket
OFF
Unit
Turns OFF when open processing has been
completed.
Services
1
Receiving Flag
ON
Unit
ON during receive processing. (Turns ON when
receive request is received.)
OFF
Unit
Turns OFF when receive processing has been
completed.
2
Sending Flag
ON
Unit
ON during send processing. (Turns ON when
send request is received.)
OFF
Unit
Turns OFF when send processing has been
completed.
3
Closing Flag
ON
Unit
ON during close processing. (Turns ON when
close request is received.)
OFF
Unit
Turns OFF when close processing has been
completed.
4 to 13
(Not used.)
---
---
---
---
14
Results Storage
Error Flag
ON
Unit
Turns ON if there is an error in storing the
results when socket services are used by
means of the CMND(490) instruction.
Section 6
Socket
Services
OFF
Unit
Turns OFF when the next request is received.
(Connected by TCP.)
15
TCP/UDP Open Flag
ON
Unit
Turns ON when open processing has been
completed.
OFF
Unit
Turns OFF when close processing has been
completed. (Stays OFF for abnormal open
processing completion.)
Note The status of these flags can also be checked using the CX-Programmer.
Opening Flag (Bit 0)
Turns ON when an open request is received either by control switch manipula-
tion or the CMND(490) instruction, and turns OFF again when the open process-
ing has been completed. When CMND(490) is used, the Results Storage Error
Flag (bit 14) will turn ON at the same time as the Opening Flag turns OFF if there
is an error in the Results Storage Area designation.
Receiving Flag (Bit 1)
Turns ON when a receive request is received either by control switch manipula-
tion or the CMND(490) instruction, and turns OFF again when the receive proc-
essing has been completed. When CMND(490) is used, the Results Storage Er-
ror Flag (bit 14) will turn ON at the same time as the Receiving Flag turns OFF if
there is an error in the Results Storage Area designation.