![Omron CS1W-ETN01 Operation Manuals Download Page 33](http://html1.mh-extra.com/html/omron/cs1w-etn01/cs1w-etn01_operation-manuals_742528033.webp)
3-1
Section
Before Operation
20
3-1
Before Operation
In order to connect the Ethernet Unit to an Ethernet network, it is necessary to
set the IP address. This section explains the process of address conversion,
which is required information for determining the Ethernet Unit’s IP address.
When using the FINS communication service, it is necessary to specify the
nodes according to the FINS address system. Even in this case, data must be
sent and received on the Ethernet network using IP addresses. Therefore, IP
addresses are converted from FINS addresses.
Ethernet Unit
Ethernet Unit
IP address: 153.211.32.114
Node number: 23
CS1-series
CPU Unit
User program
Network address: 5
Node number: 23
Data
Address conversion
To 153.211.32.114
To
To 153.211.32.114
Data
There are three ways to convert addresses, as follows:
•
Automatic generation (the default)
•
IP address table
•
Combined method (using both automatic generation and I/O address table)
Use the CX-Programmer to select the address conversion method in the System
Setup. For an explanation of how to make the setting, refer to 4-2 CPU Bus Unit
System Setup.
3-1-1 Automatic Address Generation
Automatic address generation converts addresses using the FINS node number
as the host number of the IP address. The network ID of the local IP address is
used for the network ID. The IP address of a remote node is calculated from the
local Ethernet Unit’s IP address, the subnet mask, and the remote node number
(Fins node number), as follows:
Remote IP address =
(local IP address AND subnet mask) OR remote FINS node number
Example
The remote IP address is calculated for the node using the following settings:
Local IP address:
130.25.36.8 (decimal)
Subnet mask:
255.255.255.0 (decimal)
Remote FINS node number:
5
130.25.36. 8
Local IP address
AND 255.255.255.0
Subnet mask
130.25.36.0
OR
5
Remote FINS node number
130.25.36.5
Remote IP address
Address Conversion (for
FINS Communications
Only)