![Omron CS1W-ETN01 Operation Manuals Download Page 232](http://html1.mh-extra.com/html/omron/cs1w-etn01/cs1w-etn01_operation-manuals_742528232.webp)
11-3
Section
Command/Response Reference
222
Response Codes
Response code
Description
0000
Normal
1001
Command too large
11-3-25
ADDRESS INFORMATION READ
Reads FINS node numbers and IP addresses
Command Block
65
27
Command
code
Response Block
65
27
Command
code
Response
code
Address
information
6 bytes
Number of
addresses
Parameters
Number of Addresses (Response)
The number of pairs of FINS node numbers and IP addresses being returned.
The Ethernet Unit is always 0001 (1 decimal).
Address Information
Pairs of FINS node numbers and IP addresses. Each pair requires 6 bytes and
has the following configuration.
00
FINS node
number
IP address
1
6 bytes
FINS Node Number
Node number set on the Ethernet Unit (hexadecimal).
IP Address
IP address set on the Ethernet Unit (hexadecimal).
Response Codes
Response code
Description
0000
Normal
1001