Remote I/O Communications Characteristics
Section 7-1
Maximum I/O Response Time
The maximum I/O response time occurs with the I/O timing shown in the fol-
lowing diagram.
T
IN
:
The Input Slave’s ON (OFF) delay
T
OUT
:
The Output Slave’s ON (OFF) delay
T
RM
:
The communications cycle time for the total Network (See page 305.)
T
PLC
:
The PLC’s cycle time
T
RF
:
The PLC’s DeviceNet Unit refresh time (See page 307.)
The maximum I/O response time (T
MAX
) is the total of the following terms:
T
MAX
= T
IN
+ 2
×
T
RM
+ 2
×
T
PLC
+ T
RF
+ T
OUT
Note
1.
Refer to
SECTION 4 General-purpose Slaves, SECTION 5 Environment-
resistive and Waterproof Slaves,
and
SECTION 6 Special I/O Slave Units
Specifications
for details on Input and Output Slaves’ delay times.
2.
Refer to
Refresh Time
on page 307 and the PLC’s Operation Manual for
details on the PLC’s peripheral servicing cycle time.
7-1-2
Communications Cycle Time and Refresh Time
The communications cycle time, communications time for each Slave, and
refresh time are explained in this section. All of these are necessary for calcu-
lating the time required for various processes in a DeviceNet Network.
Communications Cycle
Time
The communications cycle time is the time from the completion of a Slave’s
remote I/O communications processing until remote I/O communications with
the same Slave are processed again. The communications cycle time is used
to calculate the maximum I/O response time.
The communications cycle time depends on the number of Masters on the
Network and on whether or not message communications are being per-
formed. The following equations are valid when there is only one Master Unit.
For details on cycle time equations for multiple Master Units, refer to
page 307
.
One Master in Network
The following equations show the communications cycle time (T
RM
) when
there is only one Master in the Network. Even if the equation result is less
than 2 ms, the minimum communications cycle time (T
RM
) is 2 ms.
Master Unit processing
Input
Output
Program execution
Program execution
Program execution
PLC
T
PLC
T
PLC
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Summary of Contents for CS1W-DRM21
Page 3: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 7: ...vi Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 11: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 47: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 315: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 337: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 339: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 371: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 373: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 378: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 379: ...W347 E1 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...