337
Using Another Company’s Master Unit
Appendix B
Note
The number of bytes in the specified Read Area (Input Area) is as follows:
Produced connection size:
Read Area bytes (default: 0200 (hexadecimal))
PLC Object (0x2F)
Item
ID content
Get
(read)
Set
(write)
Value
Object instance 3
Attribute
1 State
Yes
No
---
2 Instance type
Yes
No
0100 (hexadecimal)
3 Transport class trigger
Yes
No
82 (hexadecimal)
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. characteristics
Yes
No
01 (hexadecimal)
7 Produced connection size
Yes
No
See note.
8 Consumed connection size
Yes
No
0800 (hexadecimal)
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
0000 (hexadecimal)
13 Produced connection path length
Yes
No
0000 (hexadecimal)
14 Produced connection path
Yes
No
No
15 Consumed connection path length
Yes
No
0000 (hexadecimal)
16 Consumed connection path
Yes
No
No
17 Production inhibit time
Yes
No
0000 (hexadecimal)
Item
DeviceNet service
Parameter option
Object instance 3
Service
05
Reset
No
0E
Get_Attribute_Single
No
10
Set_Attribute_Single
No
Object class
Attribute
Not supported
Service
Not supported
Item
DeviceNet service
Parameter option
Object instance 1
(CIO Area 1: IR 000 to IR 235)
See note.
Service
1C Block String Read
Logical Area Address Length
1D Block String N Read
Logical Area Address Length
1E Block String Write
Logical Area Address
1F Block String N Write
Logical Area Address
Object instance 2
(CIO Area 2: IR 300 to IR 511)
See note.
Service
1C Block String Read
Logical Area Address Length
1D Block String N Read
Logical Area Address Length
1E Block String Write
Logical Area Address
1F Block String N Write
Logical Area Address
Object instance 3
(DM Area: DM 0 to DM 6143)
See note.
Service
1C Block String Read
Logical Area Address Length
1D Block String N Read
Logical Area Address Length
1E Block String Write
Logical Area Address
1F Block String N Write
Logical Area Address
Object instance 4
(LR Area: LR 00 to LR 63)
See note.
Service
1C Block String Read
Logical Area Address Length
1D Block String N Read
Logical Area Address Length
1E Block String Write
Logical Area Address
1F Block String N Write
Logical Area Address
Object instance 5
(HR Area: HR 00 to HR 99)
See note.
Service
1C Block String Read
Logical Area Address Length
1D Block String N Read
Logical Area Address Length
1E Block String Write
Logical Area Address
1F Block String N Write
Logical Area Address
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Summary of Contents for CS1W-DRM21
Page 3: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 7: ...vi Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 11: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 47: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 315: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 337: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 339: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 371: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 373: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 378: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 379: ...W347 E1 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...