![background image](http://html1.mh-extra.com/html/omron/cs1w-drm21/cs1w-drm21_operation-manual_742357334.webp)
317
Troubleshooting
Section 8-2
Identifying Errors from Symptoms
E8
Internal non-volatile memory data error
1.Set the Read/Write Area settings using bit 00 of the soft-
ware switches.
2.Restart the Unit.
3.If the error is not cleared, replace the Unit.
F0
Duplicate node address error
Reset the node address to a number that is not used by
another Unit, and restart the Unit.
F1
Bus Off error
1.Check that the DeviceNet communications cables are
wired connected, and that noise preventative measures
have been taken.
2.Restart the Unit.
Master Unit baud rate setting error
Make sure that the baud rate settings match and restart
the Unit.
F3
Front/rear-panel DIP switch setting error
• Pin 4 of front-panel DIP switch is ON.
• Pins 1 and 2 of front-panel DIP switch are
ON.
• Pin 7 or 8 on rear-panel DIP switch is ON.
• Make sure pin 4 on the front panel, and pins 7 and 8 on
the rear panel are turned OFF.
• Turn ON or OFF pins 1 and 2 according to the correct
baud rate setting.
F6
CPU Unit interface error from noise
Remove cause of noise and restart the Unit.
If the error is not cleared, replace the C200H I/O Link Unit
or the CPU Unit.
F9
Hardware error
1.Restart the Unit
2.If the error is not cleared, replace the Unit.
Symptom
Probable Cause
Possible remedy
The power is ON, but the Slave Unit’s
indicators are all OFF.
CPU Unit error caused by noise inter-
ference.
Restart the Unit.
The Read/Write Area’s settings have
been set, but data is not being
refreshed according to the settings.
The settings have not been validated.
1.Turn ON bit 00 of the software
switches.
2.Reset the Unit.
The Unit has not been reset.
Restart the PLC or turn ON and OFF
the Unit’s Restart Bit. With C200HX/
HG/HE PLCs, these bits are in AR 01.
With CS-series PLCs, these bits are in
words A502 to A507.
After setting the areas and operating
the Unit, the data in the output area fre-
quently appears as unexpected values.
The area settings are overlapping with
those of other Communications Units.
Check the area settings of other Com-
munications Units, and correct settings
so that data is not written to an area
already being used by another Unit.
When reading the Slave’s DM Area
from the Master, unstable values are
returned and the data is unreadable.
Attempt was made to access of words
from DM 4096 onwards in the
C200HE-CPU11 CPU Unit.
Access the correct words only.
The Explicit Connection Established
Flag is ON in the C200H I/O Link Unit’s
status words, but Unit is not receiving
an explicit message from the Master.
The Network cables are disconnected,
or the Master Unit’s power supply is
OFF. (OMRON Master Units do not
have timeouts when explicit message
communications are used, so the
Explicit Connection Established Flag
will not turn OFF even if communica-
tions are stopped).
Restart the Master Unit, or connect the
cables correctly. (Timeouts cannot be
set for OMRON Master Units using
explicit message communications.)
Display
Probable cause
Possible remedy
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Summary of Contents for CS1W-DRM21
Page 3: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 7: ...vi Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 11: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 47: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 315: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 337: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 339: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 371: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 373: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 378: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 379: ...W347 E1 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...