Troubleshooting
Section 8-2
Trouble Adding a Slave to
the Network
Use the following table to troubleshoot problems in adding a Slave to the net-
work.
After the MS indicator turns green, the NS indi-
cator does not flash green - it turns red immedi-
ately.
Restart the faulty Slave Unit after checking the following points.
• Make sure that the Master and Slaves baud rate settings all match. If
they do not match, set all of the baud rates to the same value.
• Check for a node address duplication. If necessary change the node
address settings so that each node has a unique number.
• See the troubleshooting steps below under the error heading:
“The NS indicator lights green but turns red after a short time.”
• Check whether all of the Slaves’ settings are correct.
• If a particular Slave’s NS indicator is always red, replace that Slave.
The NS indicator lights green but turns red after
a short time
or
The NS indicator lights green but starts flashing
red after a short time.
• Restart the faulty Slave Unit after checking the following points.
• Make sure that there are 121-
Ω
Terminating Resistors connected at
both ends of the trunk line. Connect 121-
Ω
Terminating Resistors if
the wrong resistance is being used.
• Check whether all of the Slaves’ settings are correct.
• Check whether the communications cables are connected properly.
• Check whether the power supply is set correctly.
• Check all the nodes for broken wires in the communications and
power supply cables attached to the connectors.
• Check whether power is correctly supplied to the network.
• If there is nearby equipment that generates electrical noise, take
steps to shield the Master, Slaves, and communications cables from
the noise.
• If an error has occurred with an OMRON Master Unit, refer to the
Master Unit’s
Operation Manual. If an error has occurred in a Master
Unit supplied by another maker, refer to the relevant operation man-
ual.
• If a particular Slave’s NS indicator is always red, replace that Slave.
Error
Probable cause
Error
Probable cause
The NS indicator remains OFF.
• Check if the baud rate of the Master Unit coincides with that of the Slave
Unit. If the baud rates are different, correct the baud rate of the Slave
Unit.
• Check that the Slave’s connector is connected correctly.
• Check whether the communications power supply is supplying 24 V DC.
• Make sure that the Master is operating properly.
When using an OMRON Master, refer to the Master Unit’s
Operation
Manual. When using another company’s Master Unit, refer to that Mas-
ter’s user’s manual.
• Check whether the communications cables are connected properly.
• Check whether the power supply is set correctly.
• Check for broken wires in the communications and power supply cables
attached to the connectors.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Summary of Contents for CS1W-DRM21
Page 3: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 7: ...vi Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 11: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 47: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 315: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 337: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 339: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 371: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 373: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 378: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Page 379: ...W347 E1 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...