Serial Interface Manual
OEL8000III Series Models K/X
Command: PCC (Print Current CITLD Log)
Command Format:
PCC <enter>
Current Monthly CITLD Test readings. Final test results will be logged at the end of
the month and shown with the PCL command above.
Typical Response Message:
---SLOT: 1
XB-416 ID: 0
CANBUS START: 0X03DE
FIRMWARE: 416_E2AL
RELEASE: 2015-07-15
--CITLD REPORT 2.00
TANK 1 Diesel Fuel #2
Month: SEP, 2015
Pass Hours: 96.0
Test Height: 67.9%
Test Volume: 6737.66
Slope: 0.006(Gal/hr)
.2(Gal/hr), Thresh .1 PASSED
43 5.0 20 3.0
TANK 2 Plus 97
Month: SEP, 2015
Pass Hours: 87.0
Test Height: 74.9%
Test Volume: 7428.19
Slope: 0.003(Gal/hr)
.2(Gal/hr), Thresh .1 PASSED
83 5.0 20 3.0
If the CITLD function is not enabled in the system, the PCC or PCL commands will
return the following.
---CITLD FUNCTION IS DISABLED,
CALL OMNTEC FOR ENABLE CODE